Fault code
on the dis-
play
System character-
istics
Cause
Measures
C7
Control mode, max.
pump speed
Communication
fault
–
external
variable speed
heating circuit
pump, heating
circuit A1
Check the setting of
coding address "E5".
Cd
Control mode
Communication
fault Vitocom 100
(KM BUS)
Check connections,
Vitocom 100 and coding
address "95".
CE
Control mode
Communication
fault
–
ext. exten-
sion
Check connections and
coding address "2E".
CF
Control mode
Communication
fault, LON com-
munication mod-
ule
Replace the LON com-
munication module.
dA
Control mode with-
out room influence
Room tempera-
ture sensor, heat-
ing circuit A1
shorted out
Check the room tem-
perature sensor, heating
circuit A1.
db
Control mode with-
out room influence
Room tempera-
ture sensor, heat-
ing circuit with
mixer M2 shorted
out
Check the room tem-
perature sensor, heating
circuit with mixer M2.
dd
Control mode with-
out room influence
Room tempera-
ture sensor, heat-
ing circuit A1 lead
broken
Check the room tem-
perature sensor, heating
circuit A1 and the re-
mote control DIP switch
settings (see page 93).
dE
Control mode with-
out room influence
Room tempera-
ture sensor, heat-
ing circuit with
mixer M2 lead
broken
Check the room tem-
perature sensor, heating
circuit with mixer M2
and the remote control
DIP switch settings (see
page 93).
E4
Burner blocked
Supply voltage
fault
Replace the control unit.
Fault codes
(cont.)
71
Troubleshooting
5692
779
GB
Содержание VITOLADENS333-F
Страница 96: ...A1 Main PCB A2 Power supply unit Connection and wiring diagram external connections 96 Designs 5692 779 GB...
Страница 101: ...Parts lists cont 101 Parts lists 5692 779 GB...
Страница 102: ...Parts lists cont 102 Parts lists 5692 779 GB...
Страница 103: ...Parts lists cont 103 Parts lists 5692 779 GB...
Страница 104: ...Parts lists cont 104 Parts lists 5692 779 GB...
Страница 105: ...Parts lists cont 105 Parts lists 5692 779 GB...