Function Description
Internal Extensions EA1
(continued)
Digital data inputs DE1 to DE3
The following functions can be connected alternatively:
H
External heating program changeover for each heating
circuit
H
External blocking
H
External blocking with fault message input
H
External demand with minimum boiler water
temperature
H
Fault message input
H
Brief operation of the DHW recirculation pump
External contacts must be floating.
When connecting external contacts, observe the
requirements of safety category
II, i.e. 8.0 mm air and creep path or 2.0 mm insulation
thickness to ‘live’ parts.
Input function assignment
Select the input functions by means of codes in the
“General” group at the boiler control unit:
H
DE1: Coding address 3A
H
DE2: Coding address 3B
H
DE3: Coding address 3C
Assigning the heating program changeover function to
the heating circuits
Select the heating program changeover function for the
respective heating circuit via coding address D8 in the
“Heating circuit” group at the boiler control unit:
H
Changeover via input DE1: Code D8:1
H
Changeover via input DE2: Code D8:2
H
Changeover via input DE3: Code D8:3
The effect of the heating program changeover is selected
via coding address D5 in the “Heating circuit” group.
The duration of the changeover is set via coding address
F2 in the “Heating circuit” group.
Effect of the external blocking function on the pumps
The effect on the internal circulation pump is selected in
coding address 3E in the “General” group.
The effect on the respective heating circuit pump is
selected in coding address D6 in the “Heating circuit”
group.
The effect on a circulation pump for DHW tank heating is
selected in coding address 5E in the “DHW” group.
Effect of the external demand function on the pumps
The effect on the internal circulation pump is selected in
coding address 3F in the “General” group.
The effect on the respective heating circuit pump is
selected in coding address D7 in the “Heating circuit”
group.
The effect on a circulation pump for DHW tank heating
is selected in coding address 5F in the “DHW” group.
DHW recirculation pump runtime for brief operation
The DHW recirculation pump is started by closing the
contact at DE1, DE2 or DE3 by means of a pushbutton.
The runtime is adjusted via coding address “3D” in the
“General” group.
Output
aBJ
The following functions can be connected to output
aBJ
:
H
DHW recirculation pump
or
H
Fault message facility
Function assignment
Select the function of output
aBJ
via coding address “36”
in the “General” group at the boiler control unit.
Analog input 0 - 10 V
The 0 - 10 V hook-up provides an additional set boiler
water temperature:
0 - 1 V taken as “no default for set boiler water
temperature”
1 V
≙
set value 10°C
10 V
≙
set value 100°C
Ensure DC separation between the ground conductor and
the negative pole of the on-site voltage source.