Vitodens 200-W B2HA 112, 150 Service
47
5683 710 - 09
Coding 1
Heating Circuit 1, 2 and 3
(continued)
Coding in the factory setting
Possible change
Pump control in “Only DHW”
F6:25
In the “Only DHW” operating
mode, the circulation pump in
the heating circuit connection
set is permanently ON
F6:0
In the “Only DHW” operating
mode, the circulation pump in the
heating circuit connection set is
permanently OFF.
F6:1
to
F6:24
In the “Only DHW” operating
mode, the circulation pump in the
heating circuit connection set will
be started 1 to 24 times per day
for 10 minutes each time.
Pump control in “Standby mode”
F7:25
In the “Standby” operating
mode, the circulation pump in
the heating circuit connection
set is permanently ON
F7:0
In the “Standby” operating
mode, the circulation pump in the
heating circuit connection set is
permanently OFF.
F7:1
to
F7:24
In the “Standby” operating
mode, the circulation pump in the
heating circuit connection set will
be started 1 to 24 times per day
for 10 minutes each time.
Start temperature raising
F8:-5
Temperature limit for
terminating the reduced mode
23°F (-5ºC); see example on
page 86. Observe the setting of
coding address “A3”
F8:+10
to
F8:-60
Temperature limit adjustable from
+50 to -76°F (+10 to -60°C).
F8:-61
Function disabled.
End temperature raising
F9:-14
Temperature limit for raising the
reduced set room temperature
6.8°F (-14ºC); see example on
page 88.
F9:+10
to
F9:-60
Temperature limit for raising
the set room temperature to the
value selected for standard mode
adjustable from 50 to -76°F
(10 to -60°C).
Set flow temperature heating circuit
FA:20
Raising the set boiler water
temperature or the set flow
temperature when changing
from operation with reduced
room temperature to operation
with standard room temperature,
by 20%.
See example on page 88.
FA:0
to
FA:50
Temperature rise adjustable
from 0 to 50%.
Duration set flow temperature increase
FB:30
Duration for raising the set
boiler water temperature or
the set flow temperature (see
coding address “FA”)
60 minutes.
See example on page 88.
FB:0
to
FB:150
Duration adjustable from 0
to 300 minutes;
1 step
~