Vitodens 200-W B2HA 112, 150 Service
55
5683 710 - 09
Coding 2
Boiler
Select “Boiler”
Coding
Coding in the factory setting
Possible change
01:1
Single boiler system
01:2
Multi boiler system with Vitotronic
300-K.
04:1
Minimum burner pause subject
to the boiler load (specified by
boiler coding card)
04:0
Minimum burner pause set
permanently (specified by boiler
coding card).
06:...
Maximum limit of the boiler
water temperature, specified
in °C by the boiler coding card
06:20
to
06:127
Maximum limit of the boiler water
temperature within the ranges
specified by the boiler.
07:1
Boiler number in multi boiler
systems
07:2
to
07:8
Boiler number 2 to 8 in multi-
boiler systems.
08:...
Maximum burner heating output
in kW in the case of a multi
boiler system
08:0
to
08:199
Maximum burner heating output
adjustable from 0 to 199 kW
(limited by boiler specific
parameters) in steps of 1 kW.
0D:0
DO NOT ADJUST
--
--
0E:0
DO NOT ADJUST
--
--
13:1
DO NOT ADJUST
--
--
14:1
DO NOT ADJUST
--
--
15:1
DO NOT ADJUST
--
--
21:0
No service interval (hours run)
selected
21:1
to
21:100
Number of hours run before the
burner should be serviced is
adjustable from 100 to 10,000 h
One adjusting step
≙
100 h.
23:0
No time interval for burner
service
23:1
to
23:24
Interval adjustable from 1 to 24
months.
24:0
No “Service” display
24:1
“Service” display (the address is
automatically set and must be
manually reset after a service has
been carried out).
28:0
No burner interval ignition
28:1
to
28:24
Interval adjustable from 1 hour
to 24 hours. The burner is force
started once every 30 seconds
(only when operating with LPG).
2E:0
DO NOT ADJUST
--
--
2F:0
Venting program/fill program
disabled
2F:1
Venting program enabled.
2F:2
Fill program enabled.
30:0
Coding address should be set
to 30:0, if not adjust to 30:0
30:3
When changing from a single
boiler to a multiboiler operation,
the coding address may
automatically reset to 30:3. To
prevent continuous boiler pump
operation, adjust the coding
address for each boiler to 30:0.
31:...
NOT USED
Set speed in % of the internal
circulation pump when operated
as boiler circuit pump, specified
by the boiler coding card
31:0
to
31:100
Set speed adjustable from
0 to 100%.
38:0
Status burner control unit:
Operational (no fault)
38:
≠
0
Status burner control unit: Fault.