Vitodens 200-W B2HA 112, 150 Service
61
5683 710 - 09
Coding 2
Solar
(continued)
Coding in the factory setting
Possible change
23:4
Stop temperature differential
for central heating
backup: 4 K.
(code 20:4 must be selected)
23:2
to
23:30
Stop temperature differential
for central heating backup is
adjustable from 1 to 29 K.
24:40
Start temperature for thermostat
function 104°F (40°C).
(code 20:5 or 20:6 must be
selected)
24:0
to
24:100
Start temperature for thermostat
function adjustable from 0 to 100 K.
25:50
Stop temperature for thermostat
function 122°F (50°C).
(code 20:5 or 20:6 must be
selected)
25:0
to
25:100
Start temperature for thermostat
function is adjustable from
0 to 100 K.
26:1
Priority for DHW tank 1 with
alternate heating.
Only when setting code 20:8.
26:0
Priority for DHW tank 1 without
alternate heating.
26:2
Priority for DHW tank 2 without
alternate heating.
26:3
Priority for DHW tank 2 with
alternate heating.
26:4
Alternate heating without priority
for one of the DHW tank.
27:15
Alternate heating time 15 minutes.
The DHW tank without priority
is heated at most for the
duration of the set alternate
heating time if the DHW tank
with priority is heated up.
27:5
to
27:60
The alternate heating time is
adjustable from 5 to 60 minutes.
28:3
Alternate pause time 3 minutes
After the selected alternate
heating time for the DHW tank
without priority has expired, the
rise in collector temperature is
captured during the alternate
pause time.
28:1
to
28:60
The alternate pause time is
adjustable from 1 to 60 minutes.