Vitodens 200-W B2HA 112, 150 Service
5683 710 - 09
66
Coding 2
Heating Circuit 1, 2 and 3
(continued)
Coding in the factory setting
Possible change
E5:0
Do not adjust
--
--
E6:...
NOT USED
Maximum speed of the variable
speed heating circuit pump in
% of the maximum speed in
standard mode. Value is
specified by boiler-specific
parameters
E6:0
to
E6:100
Maximum speed adjustable
from 0 to 100%.
E7:50
NOT USED
Minimum speed of the variable
speed heating circuit pump:
30% of the maximum speed
E7:0
to
E7:100
Minimum speed adjustable from
0 to 100% of the maximum
speed.
E8:1
NOT USED
Minimum speed in operation
with reduced room temperature
subject to the setting in coding
address “E9”
E8:0
Speed subject to the setting in
coding address “E7”.
E9:45
NOT USED
Speed of the variable speed
heating circuit pump: 45% of
the maximum speed during
operation with reduced room
temperature
E9:0
to
E9:100
Speed adjustable from 0 to 100%
of the maximum speed during
operation with reduced room
temperature.
F1:0
Slab curing function disabled
F1:1
to
F1:6
Slab curing adjustable in
accordance with 6 selectable
temperature/time profiles.
F1:15
Constant flow temperature 68°F
(20°C).
F2:8
Time limit for party mode
or external heating program
changeover via pushbutton:
8 h
*1
F2:0
No time limit for party mode
*1.
F2:1
to
F2:12
Time limit adjustable from 1 to
12 h
*1.
F5:12
Run-on time of the boiler circuit
pump in heating mode: 12
minutes.
F5:0
No run-on time for the circulation
pump in the heating circuit
connection set.
F5:1
to
F5:20
Run-on time of the circulation pump
in the heating circuit connection set
adjustable from 1 to 20 minutes.
*1
Party mode ends automatically in the “Heating and DHW” program, when the system changes over to operation with
standard room temperature.