Vitodens 200-W B2HA 112, 150 Service
53
5683 710 - 09
Coding 2
General
(continued)
Coding in the factory setting
Possible change
77:1
LON participant number
77:2
to
77:99
LON participant number,
adjustable from 1 to 99:
1 - 4 = Boiler
5 = Cascade
10 - 98 = Vitotronic 200-H
99 = Vitocom
Note:
Allocate each number only
once.
79:1
With LON communication
module: Control unit is fault
manager
79:0
Control unit is not fault manager.
7B:1
With LON communication
module: Control unit transmits
the time
7B:0
Does not transmit time.
7E:0
NOT USED
Without flue gas cascade
or with flue gas cascade
with negative pressure
(only for multi boiler systems)
7E:1
With positive pressure flue
gas cascade.
7F:1
Detached house
7F:0
Apartment building
Separate adjustment of holiday
program and time program for
DHW heating possible.
80:6
A fault message is displayed
if a fault is active for at least
30 seconds
80:0
Immediate fault message.
80:2
to
80:199
Minimum fault duration until fault
message occurs, adjustable
from 10 s to 995 s; 1 step
≙
5
seconds.
81:1
NOT USED
Automatic summer/wintertime
changeover
81:0
Manual summer/wintertime
changeover.
81:2
Use of the radio clock receiver
(automatic recognition).
81:3
With LON communication module:
The control unit receives the time.
82:0
Operation with natural gas
82:1
Operation with LPG (only
adjustable if coding address 11:9
has been set).
86:0
DO NOT ADJUST
--
--
87:0
DO NOT ADJUST
--
--
88:0
Temperature display in °C
(Celsius)
88:1
Temperature display in °F
(Fahrenheit).