Vitodens 200-W B2HA 112, 150 Service
5683 710 - 09
56
Coding 2
DHW
Select “DHW”
Coding
Coding in the factory setting
Possible change
56:0
Set DHW temperature
adjustable from 50 to 140° F
(10 to 60° C)
56:1
Set DHW temperature adjustable
from 50 to over 140° F (10 to
over 60° C)
Note:
Maximum value subject to
boiler coding card. Observe
the maximum permissible
DHW temperature.
58:0
Without auxiliary function for
DHW heating
58:10
to
58:60
Input of a second set DHW
temperature, adjustable from 50
to 140°F (10 to 60°C) (observe
coding addresses “56” and “63”).
59:0
DHW tank heating:
Starting point -2.5 K
Stopping point +2.5 K
59:1
to
59:10
Starting point adjustable from
1 to 10 K below the set value.
5b:0
DHW tank directly connected
to the boiler
5B:1
DHW tank connected downstream
of the low loss header.
5E:0
Circulation pump for DHW tank
heating stays in control mode
at signal “External blocking”
5E:1
Circulation pump for DHW
tank heating stops at signal
“External blocking”.
5E:2
Circulation pump for DHW
tank heating starts at signal
“External blocking”.
5F:0
Circulation pump for DHW tank
heating stays in control mode
at signal “External demand”
5F:1
Circulation pump for DHW
tank heating stops at signal
“External demand”.
5F:2
Circulation pump for DHW
tank heating starts at signal
“External demand”.
60:20
During DHW heating, the boiler
water temperature is maximum
20 K higher than the set DHW
temperature
60:5
to
60:25
The differential between the boiler
water temperature and the set
DHW temperature is adjustable
from 5 to 25 K.
62:2
Circulation pump with 2 minutes
run-on time after DHW tank
heating
62:0
Circulation pump without run-on.
62:1
to
62:15
Run-on time adjustable from 1 to
15 minutes.