Coding 2
Solar
Select “Solar”
Note:
The solar group is only displayed if a solar control module, type SM1, is connected.
Coding
Coding in the factory setting
Possible change
00:8
The solar circuit pump starts
when the collector temperature
exceeds the actual DHW tank
temperature by 8 K.
00:2
to
00:30
The differential between
the actual DHW tank temperature
and the start point for the solar
circuit pump can be adjusted from
2 to 30 K.
01:4
The solar circuit pump is switched
off when the differential between
the collector temperature and the
actual DHW tank temperature is
less than 4 K.
01:1
to
01:29
The differential between the
actual DHW tank temperature and
the stop point for the solar circuit
pump can be adjusted from 1 to
29 K.
02:0
Solar circuit pump (stepped)
is not speed-controlled
02:1
Solar circuit pump is speed-
controlled with wave packet
control.
02:2
Solar circuit pump is speed-
controlled with PWM control.
03:10
The temperature differential
between the collector
temperature and actual DHW
tank temperature is regulated
to 10 K.
03:5
to
03:20
The differential temperature
control between collector
temperature and actual DHW tank
temperature can be adjusted from
5 to 20 K.
04:4
Controller amplification of the
speed control 4%/K.
04:1
to
04:10
Controller amplification adjustable
from 1 to 10%/K.
05:10
Minimum speed of the solar
circuit pump 10% of the
maximum speed.
05:2
to
05:100
Minimum speed of the solar
circuit pump is adjustable from
2 to 100%.
06:75
Maximum speed of the solar
circuit pump 75% of the
maximum possible speed.
06:1
to
06:100
Maximum speed of the solar
circuit pump is adjustable from 1
to 100%.
07:0
Interval function of the solar
circuit pump switched off.
07:1
Interval function of the solar
circuit pump switched on. To
capture the collector temperature
more accurately, the solar circuit
pump starts for short cycles.
08:60
The solar circuit pump is
switched off when the
actual DHW tank temperature
reaches 140°F (60°C)
(maximum DHW tank
temperature).
08:10
to
08:90
The maximum DHW tank
temperature can be adjusted
from 50 to 194°F (10 to 90°C).