57
B
C
A
Fig. 53
1.
Pivot the control unit forwards.
2.
Pull off drain hose
A
.
3.
Pull off retaining clip
B
.
4.
Remove trap bottle
C
downwards.
5.
Fill trap with water and refit.
6.
Reconnect drain hose
A
.
7.
Check that the condensate pipe is correctly
attached to the trap and heat exchanger.
Note
Route the drain hose without any bends and with a
constant fall.
8.
Remount the cover panel.
9.
Secure the control unit back in the operating posi-
tion.
Commissioning, inspection, maintenance
Filling the trap on the gas condensing module with water
5775 636 GB