108
Coding in the delivered condition
Possible change
d5:0
With external heating program
changeover.
Observe settings of coding ad-
dresses "3A", "3b" and "3C" in
"General"
group.
Operating program switches to
"constant central heating at re-
duced room temperature" or
"standby mode" depending on the
setting of the reduced set room
temperature.
d5:1
Operating program switches to "con-
stant operation with standard room
temperature".
d6:0
Heating circuit pump stays in con-
trol mode at "External blocking"
signal.
d6:1
Heating circuit pump stops on signal
"External blocking", depending on
coding addresses "3A", "3b" and
"3C".
d6:2
Heating circuit pump starts on signal
"External blocking", depending on
coding addresses "3A", "3b" and
"3C".
d7:0
Heating circuit pump stays in con-
trol mode at "External demand"
signal.
d7:1
Heating circuit pump stops on signal
"External demand", depending on
coding addresses "3A", "3b" and
"3C".
d7:2
Heating circuit pump stops on signal
"External demand", depending on
coding addresses "3A", "3b" and
"3C".
d8:0
With EA1 extension:
No operating program changeover
d8:1
Operating program changeover via
input DE1
d8:2
Operating program changeover via
input DE2
d8:3
Operating program changeover via
input DE3
E1:1
Never adjust
E2:50
With remote control:
No display correction for the actual
room temperature (only for weath-
er-compensated control units)
E2:0
to
E2:49
Display correction
–
5 K
to
Display correction
–
0.1 K
E2:51
to
E2:99
Display corr0.1 K
to
Display corr4.9 K
E5:0
Never adjust
E6:...
Only for heating systems without a
heating circuit with mixer:
Max. speed of internal variable
speed heating circuit pump as % of
max. speed in standard mode. Val-
ue is specified by boiler-specific
parameters (only for weather-com-
pensated control unit).
E6:0
to
E6:100
Maximum speed adjustable from 0
to 100 %
E7:30
Only for heating systems without a
heating circuit with mixer:
Min. speed of the internal variable
speed heating circuit pump:
E7:0
to
E7:100
Min. speed adjustable from 0 to
100 % of max. speed
Codes
Coding level 2
(cont.)
5775 636 GB
Codes
Содержание C3TB
Страница 44: ...44 3 5 1 2x 2 4 7 6 Fig 43 Installation sequence Fitting the front panels 5775 636 GB Installation ...
Страница 48: ...48 14 Fig 47 Installation sequence If required for easier handling Dismantling cont 5775 636 GB Installation ...
Страница 136: ...136 Troubleshooting Repairs gas condensing module cont 5775 636 GB Diagnosis ...
Страница 143: ...143 Parts lists Heat cell assembly 5775 636 GB Components ...
Страница 148: ...148 0001 0001 0003 0003 0002 0002 0004 Fig 118 Parts lists External connection assembly 5775 636 GB Components ...