37
!
Please note
Live contacts lead to short circuits or phase fail-
ure.
The external connection
must be floating
and
meet the requirements of protection class II.
Plug
lH
EA1 extension
A
lH
N
?
1 L
A
Floating contact (when connected, remove jumper
between L and 1)
B
[{S
DE
[{D
DE
[{A
DE
A
A
Floating contact
B
EA1 extension
Codes
■
"4b:2" in group
"General"/1
■
Effect of the function on the heating circuit pump:
Coding address "d6" in group
"Heating circuit"
(only
for weather-compensated control units)
■
Effect of the function on the circulation pump for cylin-
der heating:
Coding address "5E" in group
"DHW"/3
Codes
■
Set "3A" (DE1), "3b" (DE2) or "3C" (DE3) to 3 or 4 in
group
"General"/1
.
■
Effect of the function on the heating circuit pump:
Coding address "d6" in group
"Heating circuit"
(only
for weather-compensated control units)
■
Effect of the function on the circulation pump for cylin-
der heating:
Coding address "5E" in group
"DHW"/3
Power supply for accessories (230 V ~)
156
156
156
40
X4
8 7 6 5 4 3 2 1
X1
X3
K
T6,3 A
Fig. 35
Power cables for accessories can be connected to
plug
aBH
on the distribution board. This connection is
switched using the ON/OFF switch on the control unit
of the gas condensing module.
If the total system current exceeds 6 A, connect one or
more extensions directly to the mains supply via an
ON/OFF switch.
Installation sequence
Electrical connections
(cont.)
5775 636 GB
Installation
Содержание C3TB
Страница 44: ...44 3 5 1 2x 2 4 7 6 Fig 43 Installation sequence Fitting the front panels 5775 636 GB Installation ...
Страница 48: ...48 14 Fig 47 Installation sequence If required for easier handling Dismantling cont 5775 636 GB Installation ...
Страница 136: ...136 Troubleshooting Repairs gas condensing module cont 5775 636 GB Diagnosis ...
Страница 143: ...143 Parts lists Heat cell assembly 5775 636 GB Components ...
Страница 148: ...148 0001 0001 0003 0003 0002 0002 0004 Fig 118 Parts lists External connection assembly 5775 636 GB Components ...
Страница 154: ...154 0006 0003 0005 0001 0002 0004 Fig 121 Parts lists Miscellaneous assembly 5775 636 GB Components ...
Страница 160: ...160 Parts not shown 0009 PCB IU100 B30 Parts lists Fuel cell assembly 5775 636 GB Components ...
Страница 161: ...161 Parts lists Fuel cell assembly cont 5775 636 GB Components ...
Страница 187: ...187 5775 636 GB ...