135
2.
At plug
gS
, swap the cores at terminals "
|
" and
"
~
".
3.
Refit the casing cover.
Check flow temperature sensor
10
1
10
30
50
70
90
110
Temperature in °C
0.4
0.6
0.8
2
4
6
8
20
Resistance
in kΩ
Fig. 112 Sensor type: NTC 10 k
Ω
1.
Disconnect plug
?
(flow temperature sensor).
2.
Check the sensor resistance and compare it to the
curve.
In the event of severe deviation replace the sensor.
Checking the Vitotronic 200-H (accessories)
The Vitotronic 200-H is connected to the control unit
via the LON cable. To test the connection, carry out a
subscriber check at the boiler control unit (see
page 74).
Troubleshooting
Repairs (gas condensing module)
(cont.)
5775 636 GB
Diagnosis
Содержание C3TB
Страница 44: ...44 3 5 1 2x 2 4 7 6 Fig 43 Installation sequence Fitting the front panels 5775 636 GB Installation ...
Страница 48: ...48 14 Fig 47 Installation sequence If required for easier handling Dismantling cont 5775 636 GB Installation ...
Страница 136: ...136 Troubleshooting Repairs gas condensing module cont 5775 636 GB Diagnosis ...
Страница 143: ...143 Parts lists Heat cell assembly 5775 636 GB Components ...
Страница 148: ...148 0001 0001 0003 0003 0002 0002 0004 Fig 118 Parts lists External connection assembly 5775 636 GB Components ...
Страница 154: ...154 0006 0003 0005 0001 0002 0004 Fig 121 Parts lists Miscellaneous assembly 5775 636 GB Components ...
Страница 160: ...160 Parts not shown 0009 PCB IU100 B30 Parts lists Fuel cell assembly 5775 636 GB Components ...
Страница 161: ...161 Parts lists Fuel cell assembly cont 5775 636 GB Components ...
Страница 187: ...187 5775 636 GB ...