117
Fault code dis-
played
System characteristics
Cause
Measures
7F
Circulation pump for dis-
charging buffer stopped
Lead break on top buffer
temperature sensor
)
A
Check top buffer temperature sen-
sor (see page 130).
80
Circulation pump for dis-
charging buffer stopped
Short circuit on bottom
buffer temperature sen-
sor
)
B
Check bottom buffer temperature
sensor (see page 130).
81
Circulation pump for dis-
charging buffer stopped
Lead break on bottom buf-
fer temperature sen-
sor
)
B
Check bottom buffer temperature
sensor (see page 130).
A2
Emergency mode with insuffi-
cient system pressure
System pressure too low
Top up with water.
A3
Burner blocked
Flue gas temperature sen-
sor incorrectly positioned
Fit flue gas temperature sensor
correctly (see page 131).
A4
Control mode
Max. system pressure ex-
ceeded
Check the system pressure.
Check the function and sizing of
the expansion vessel.
Vent the heating system.
Coding address "0E" is set to "1" to
document the fault. Must be man-
ually reset to "0" after troubleshoot-
ing.
A7
Control mode as per deliv-
ered condition
Programming unit faulty
Replace the programming unit.
A8
Burner blocked. Venting pro-
gram starts automatically.
Air in the internal circula-
tion pump or minimum
flow rate not achieved
Vent the system if the fault mes-
sage persists.
A9
If a heating circuit with mixer
is connected, the burner op-
erates at its lower heating
output.
If only one heating circuit
without mixer is connected,
the burner is blocked.
Internal circulation pump
blocked
Check circulation pump.
b0
Burner blocked
Short circuit, flue gas tem-
perature sensor
Check the flue gas temperature
sensor (see page 131).
b1
Control mode as per deliv-
ered condition
Communication error, pro-
gramming unit
Check connections; replace pro-
gramming unit if necessary.
b4
Regulates as if the outside
temperature were 0 °C.
Internal fault
Replace control unit.
b5
Control mode as per deliv-
ered condition
Internal fault
Replace control unit.
b7
Burner blocked
Coding card fault
Plug in or replace the coding card.
b8
Burner blocked
Lead break, flue gas tem-
perature sensor
Check the flue gas temperature
sensor (see page 131).
bA
Mixer regulates to 20 °C flow
temperature.
Communication error, mix-
er extension kit for heating
circuit 2 (with mixer)
Check mixer extension kit connec-
tions and code.
bb
Mixer regulates to 20 °C flow
temperature.
Communication error, mix-
er extension kit for heating
circuit 3 (with mixer)
Check mixer extension kit connec-
tions and code.
Troubleshooting
Fault codes for gas condensing module
(cont.)
5775 636 GB
Diagnosis
Содержание C3TB
Страница 44: ...44 3 5 1 2x 2 4 7 6 Fig 43 Installation sequence Fitting the front panels 5775 636 GB Installation ...
Страница 48: ...48 14 Fig 47 Installation sequence If required for easier handling Dismantling cont 5775 636 GB Installation ...
Страница 136: ...136 Troubleshooting Repairs gas condensing module cont 5775 636 GB Diagnosis ...
Страница 143: ...143 Parts lists Heat cell assembly 5775 636 GB Components ...
Страница 148: ...148 0001 0001 0003 0003 0002 0002 0004 Fig 118 Parts lists External connection assembly 5775 636 GB Components ...
Страница 154: ...154 0006 0003 0005 0001 0002 0004 Fig 121 Parts lists Miscellaneous assembly 5775 636 GB Components ...
Страница 160: ...160 Parts not shown 0009 PCB IU100 B30 Parts lists Fuel cell assembly 5775 636 GB Components ...
Страница 161: ...161 Parts lists Fuel cell assembly cont 5775 636 GB Components ...
Страница 187: ...187 5775 636 GB ...