VD120 Series Inverter User Manual Parameter Description
-
135
-
FF-10
Date of Production
(Date)
0~31
Factory
Setting
●
Product information.
FF-11
Inverter Module Radiator
Temperature
0°C~120°C
0
●
Inverter module temperature.
FF-13
Accumulative Power
Consumption
0°C~65535°C
0°C
●
Show the inverter accumulative power consumption so far.
FF-14
Accumulative Running
Time
0h~65535h
0h
●
Display the accumulative running time of frequency converter since the factory.
When this time reach to set running time (Fb-35), inverter multi-function digital output function (30)
output ON signal.
FF-15
Accumulative Power-on
Time
0h~65535h
0h
●
Display the accumulative power time of frequency inverter since the factory.
When this time reach to set running time (Fb-34), inverter multi-function digital output function (31)
output ON signal.
FP Factory Parameter Group
Factory set parameters, users don’t need to modify, forbidden user tries to enter the parametes group
to view or modify any of the data, otherwise it will bring unexpected circumstances and even serious
fault.
A0 Motor 1 Torque Control Parameter Group
A0-00
Speed/Torque Control
Mode Selection
0: Speed control
1: Torque control
0
◎
Used to select the inverter control mode: speed control or torque control.
VD120’s multi-function digital DI terminal, have two function associated with torque control: torque
control prohibit (function 40), speed control/torque control switch (function 39). The two terminals
should be use in conjunction with A0-00 to realize the switch between speed and torque control.
When the speed control/torque control switch terminal is invalid, the control mode is determined by
A0-00, if the speed control switch/torque control switch is effective, the control mode is equivalent to
the value of A0-00.
In any case, the frequency inverter is fixed to the speed control mode when the torque control prohibit
terminal is valid.
Содержание VD120 Series
Страница 2: ......