Communication Protocol VD120 Series Inverter User Manual
-
168
-
When the function code set to valid values, if a communication and the interval time of the next
communication beyond the communication timeout time, system will be reported to the
communication failures (Err.18). Usually, it is set to invalid. If you set this parameter in a system with
continuous communication, you can monitor the communication status.
Fd-05
Data Transfer Format
Selection
0: Non standard MODBUS protocol
1: Standard MODBUS protocol
1
○
Fd-05=1: Selects the standard Modbus protocol.
Fd-05=0: When read command, the slave returns one byte more than the standard Modbus protocol,
refer to "Communication Data Structure" of this protocol.
Fd-06
Communication Read
Current Resolution
0: 0.01A
1: 0.1A
0
○
Used to determine the output unit of the current value when communication reads the output current.