VD120 Series Inverter User Manual Parameter Description
-
143
-
Different from ordinary digital quantity input terminals, the state of the virtual VDI can set two ways,
and selection by b1-05.
When selecting VDI status is decided by the state of the corresponding virtual VDO, VDI whether is
valid state, depending on the VDO output as valid or invalid, and the VDIx only binding VDOx (x is 1~
5).
When selection VDI status are setting by the function code, through the binary system of function
code b1-06, determine the status of the virtual input terminals respectively.
The following illustrates the use method of virtual VDI.
Example 1: when selecting VDO state decided to VDI, to complete the following functions: “AI1 input
beyond the upper and lower limit, frequency inverter fault alarm and stop", can use the following
setting method:
Set VDI1 function to "user-defined failure 1" (b1-00 = 50);
Set VDI1 terminal valid state model for determine by VDO1 (b1-05 = xxx0);
Set VDO1 output function as "AI1 input beyond the upper and lower limit" (b1-11= 37);
When AI1 input beyond the upper and lower limit, the VDO1 output is ON state, the VDI1 input
terminal state is valid, inverter VDI1 receives the user-defined failure 1, the inverter will fault alarm Err.
35 and stop.
Example 2: when selecting function code b1-06 set VDI state, to complete the following functions:
"after inverter power on, automatically enter the running state", can use the following setting method:
Set VDI1 function to " forward running " (b1-00=1);
Set VDI1 terminal valid state mode is setting for function code (b1-05=xxx1);
Set VDI1 terminal status for valid (b1-06=xxx1);
Set the command source for "terminal control" (F0-01=1);
After inverter power on and finished initialization, detect VDI1 is effective, and the terminal
corresponding to forward running, equivalent to a frequency inverter receives a terminal forward
running command, frequency inverter immediately began to forward running.
b1-07
Function Selection when
AI1 Terminal as DI
0~59
0
◎
b1-10
Effective Mode Selection
when AI1 Terminal as DI
0: High electrical level enable
1: Low electrical level enable
0
◎
As the group function code is used to AI used as DI, when AI used as DI, when the AI input voltage is
greater than 7V, AI terminal state for high level, when the AI input voltage is lower than 3V, AI terminal
state for low level. Between 3V~7V for hysteresis A1-10 when used to determine the AI as DI, AI high
level state for valid state, or the low level for valid state.
As for AI as the function set of DI, same as the ordinary DI settings, please refer to the instructions of
F5 group related DI setup.
The following figure is take AI input voltage as an example, explaine the relationship between AI input
voltage and the corresponding DI state.
Содержание VD120 Series
Страница 2: ......