VD120 Series Inverter User Manual Parameter Description
-
91
-
21
Acceleration and
deceleration time
selection terminal
1
22
Acceleration and
deceleration time
selection terminal
2
It can realize 4 kinds of acceleration/deceleration time selection
through the 4 states of two terminals.
23
PULSE
frequency input
(Only effective for
HDI1)
HDI1 as the function of the pulse input terminals.
24
Control command
switch terminal 1
Used to switch between the keypad control and terminal control. If
command source selection for the keypad control, then switch
system for terminal control when terminal is effective; vice versa.
25
Control command
switch terminal 2
Used to switch between the terminal control and communication
control. If command source selection for the terminal control, then
switch system for communication control when terminal is effective;
vice versa.
26
Immediate DC
braking
This terminal is valid, and the inverter directly switchover to the DC
braking state.
27
Deceleration DC
braking
The terminal is valid, slow down to stop inverter and DC braking
starting frequency, and then switchover to DC braking state.
28
External stop
terminal 1 (Only
effective for
keypad control)
Can use the terminal to make inverter downtime when the keypad
control, equivalent to the STOP key function on the keypad.
29
External stop
terminal 2
(According to the
deceleration time
4)
In any control mode (panel control, terminal control,
communication control), can use the terminal to make the
frequency inverter deceleration and stop, then the deceleration
time fixed for deceleration time 4 at this time.
30
Emergency stop
The terminal is enabled, inverter stop at Fb-09 set time.
31
PID pause
PID temporary failure, the inverter to maintain the current output
frequency, the PID adjustment of frequency source no longer.
32
PID integral
pause
When terminal is valid, then the integral regulating function of PID
suspended, but the proportion adjustment and the differential
adjustment function of PID is still valid.
33
Reverse PID
action direction
The terminal is valid, PID action direction and the direction of
FA-03 set is opposite.
34
PID parameter
switching
When PID parameter switching condition is DI terminal (FA-18=1),
and the terminal is invalid, PID parameter using the FA-05~FA-07;
when terminal is valid, then use the FA-15~FA-17.
35
PLC pause
PID temporary failure, the inverter to maintain the current output
frequency, the PID adjustment of frequency source no longer.