VD120 Series Inverter User Manual Function Parameter Table
-
39
-
Hundred’s digit: reserved
Thousand’s digit: reserved
Ten thousand’s digit: reserved
F9-40
Continue
Running
Frequency
Selection at
Failure
0: Run to the current running
frequency
1: Run at set frequency
2: Run at frequency upper limit
3: Run at frequency lower limit
4: Run at abnormal standby
frequency
0
○
F9-41
Abnormal
Standby
Frequency
0.0%~100.0%
(100.0% corresponding max
frequency F0-10)
100.0%
○
FA Process PID
Function
Code
Parameter
Name
Setting Range
Factory
Default Value
Property
FA-00
PID Given
Source
0: FA-01 setting
1: AI1
2: Reserved
3: Reserved
4: PULSE setting
5: Communication setting
6: Multi-reference setting
7: Keypad potentiometer
0
○
FA-01
PID Digital
Giving
0.0%~100.0%
50.0%
○
FA-02
PID Feedback
Source
0: A1
1: Reserved
2: Reserved
3: Reserved
4: PULSE setting
5: Communication setting
0
○
FA-03
PID Action
Direction
0: Positive action
1: Anti-action
0
○
FA-04
PID Given
Feedback
Range
0~65535
1000
○
FA-05
Proportion
Gain Kp1
0.0~100.0
20.0
○
FA-06
Integral Time
Ti1
0.01s~10.00s
2.00s
○
FA-07
Differential
0.000s~10.000s
0.000s
○