Function Parameter Table VD120 Series Inverter User Manual
-
28
-
Code
Name
Default Value
F6-00
DO1 Terminals
Output Mode
Selection
0: HDO1 pulse output (optional)
1: Switch output
1
○
F6-01
DO1 Output
Terminals
Function
Selection
0
○
F6-02
Relay T1
Function
Selection
0: No output
1: Inverter in running
2: Ready for run
3: Fault output 1 (no output when
continue to run )
4: Fault output 2 (no output
undervoltage or continue to run)
5: Warning output 3 (output when
fault)
6: Output undervoltage
7: Frequency level detection FDT1
output
8: Frequency level detection FDT2
output
9: Frequency reached
10: Frequency 1 reached output
11: Frequency 2 reached output
12: Zero speed running 1 (no output
when stop)
13: Zero speed running 2 (output
when stop)
14: Frequency upper limit reached
15: Frequency lower limit reached 1
(no output when stop)
16: Frequency lower limit reached 2
(output when stop)
17: Current 1 reached output
18: Current 2 reached output
19: Zero current state
20: Output current limit exceeded
21: Motor overload pre-alarm
22: Inverter overload pre-alarm
23: During the load
24: Set Count value reached
25: Designated count value reached
26: Length reached
27: Module temperature reached
28: Reserved
29: Current running time reached
30: Accumulative running time
reached
31: Accumulative power-on time
0
○