22  

••••

  Installation

XX002 Rev 799 Surveyor99 Dome System

INDOOR PENDANT MODEL 

The Indoor Pendant Model mounts on a Vicon Mount or a 1.0-inch vertical Pipe. The pipe is a standard 1.0-
inch NPT type and must be oriented vertically so the Surveyor99 can effectively hang from the pipe.

The Mount is installed with all the cables run through it and the 1.0-inch NPT Pipe is prepared for Surveyor99
installation. The cables are routed through the Housing and the Housing is screwed tightly to the pipe. Then
the Surveyor99 is hung from the Housing Safety Cord while it is wired and configured. The Surveyor99 is then
carefully snapped into the Housing. The Surveyor99 is supported by the Mount. The Indoor Lower Dome is
then anchored with its Safety Cord and snapped on. Refer to Figure 20. Detailed installation instructions will
follow.

The Accessory Kit containing the RJ-45 to RJ-45 8 foot (2.4 m) cable and RJ-45 Termination Box can be used
for wiring the 4 alarms or the relay in this installation. Since the supplied cable is limited to 8 feet (2.4 m), the
Termination Box must be mounted within the immediate area of the Surveyor99. The Mount must provide a
support of suitable strength for the Housing and the Surveyor99 weight of 6.0 lb (2.7 kg).

1.  Install the Mount in accordance with the

Installation Manual included with the Mount or
prepare the vertical 1.0-inch NPT Pipe.

 
2.  Feed all necessary cables through the back

of the Mount and out the end of the 1.0-inch
NPT Pipe, 16-inches (406 mm) in length.

 
3.  Lift the Housing up to the Mount or Pipe and

feed the cables through its top opening.

 
4.  Place the Housing onto the 1.0-inch pipe and

screw clockwise, looking up at the Housing.
When it becomes snug, turn it an additional
quarter-turn.

 
5.  Verify that each cable drops from the pipe

opening at least 16-inches (406 mm) in
length.

 
6.  Lift the Surveyor99 up to the Housing and

attach the Housing’s Safety Cord to the
Surveyor99’s Latch. Allow the Surveyor99 to
hang from the Housing.

 
7.  Route each cable from the inside top of the

Housing down to the Cable Clamp on the Enclosure and then comfortably over to its mating connector on
the Communications/Power Supply Board. Add 1-inch (25 mm) of extra length to each cable for
termination and cut them. The approximate length of each cable should be 13 - 16-inches (330 - 406 mm).

 
8.  Terminate all the cables as follows:
 

a)  Remove Terminal Blocks TB1 and/or TB3. Since the control signals exist in both TB3 and J3, do not

remove TB3 if J3 will be used for control signal wiring.

Figure 20

Indoor Pendant Mount Model

Содержание Surveyor 99

Страница 1: ...en designed to be used in life critical situations and must not be used for this purpose Copyright 1999 Vicon Industries Inc All rights reserved Product specifications subject to change without notice...

Страница 2: ......

Страница 3: ......

Страница 4: ......

Страница 5: ...turning equipment off and on the user is encouraged to try and correct the interference by one or more of the following measures Reorient the receiving antenna Relocate the equipment with respect to...

Страница 6: ......

Страница 7: ...it 2 Unpacking and Inspection 2 Surveyor99 Components 3 Enclosure 3 Camera Drive 3 Shroud 3 Lower Dome 3 Housing 4 Sunshield 4 INSTALLATION 5 Quick Installation 5 In Ceiling Mount Model no ceiling acc...

Страница 8: ...85 Mode 39 For Vicoax Mode 39 Setting the End of Line Jumpers JP1 JP2 JP3 for RS 485 Protocol Operation 41 DISASSEMBLING THE SURVEYOR99 43 For an In Ceiling Installation 43 For a Pendant Installation...

Страница 9: ...y location where it may be exposed to water or moisture This does not apply to outdoor camera housings outdoor pan and tilt drives and other equipment designed for direct exposure to outdoor environme...

Страница 10: ...d result in a fire or electric shock Never spill liquid of any kind on the video product 18 Servicing Do not attempt to service this video product yourself as opening or removing covers may expose you...

Страница 11: ...the installation site NOTE Read all instructions before beginning any installation How to Use this Manual This manual was designed to provide the best overall instructions for the installation and ope...

Страница 12: ...g Mount Model when Flexible Conduit Pipe will not be used Refer to the In Ceiling Mount Model sub section of the Installation Section for details on installing this fitting The Teflon Tape is used for...

Страница 13: ...f Fitting is provided in the Accessory Kit The supplied Strain Relief Fitting Romex cable fitting provides sufficient cable anchoring at the Enclosure The Ceiling Clips are used to give a convenient a...

Страница 14: ...ipped with a Safety Cord and Clip which is used to suspend the Enclosure during installation Sunshield The Sunshield is used on the Outdoor Pendant version and mounts over the Housing It incorporates...

Страница 15: ...ain Relief Fitting and re install Top Cover b Hold Enclosure up to ceiling and route approximately 9 inches 229 mm of cables through Strain Relief Fitting Tighten 2 Strain Relief Fitting screws 3 If F...

Страница 16: ...Lower Dome handling This Surveyor99 is shown with typical wiring and configuration using Flexible Conduit See Figure 4 The DIP switches are set as follows DIP SWITCH S1 Surveyor99 address 1 ON 2 OFF...

Страница 17: ...in Relief Fitting Tighten 2 Strain Relief Fitting screws 4 If Flexible Conduit Pipe is used a Route approximately 9 inches 229 mm of Conduit cables through Conduit Fitting b Insert end of Flexible Con...

Страница 18: ...Connector See Figure 6 The DIP switches are set as follows DIP SWITCH S1 Surveyor99 address 1 ON 2 OFF 4 OFF 8 OFF 16 OFF 32 OFF 64 OFF 128 OFF THIS IS ADDRESS 1 DIP SWITCH S2 Surveyor99 configuration...

Страница 19: ...ong enough to reach their mating connector See Figure 8 Install all connectors into Communication Power Supply Board and place each into the Cable Clamp If necessary check wiring against data in Table...

Страница 20: ...See Figure 9 The DIP switches are set as follows DIP SWITCH S1 Surveyor99 address 1 ON 2 OFF 4 OFF 8 OFF 16 OFF 32 OFF 64 OFF 128 OFF THIS IS ADDRESS 1 DIP SWITCH S2 Surveyor99 configuration 1 ON NTS...

Страница 21: ...Camera Drive s Latch 5 Cut and terminate all cables See Figure 11 All cables should be just long enough to reach their mating connector If necessary check wiring against data in Table 1 of Wiring Sec...

Страница 22: ...See Figure 12 The DIP switches are set as follows DIP SWITCH S1 Surveyor99 address 1 ON 2 OFF 4 OFF 8 OFF 16 OFF 32 OFF 64 OFF 128 OFF THIS IS ADDRESS 1 DIP SWITCH S2 Surveyor99 configuration 1 ON NTS...

Страница 23: ...tight to the surface Then the Camera Drive is hung from the Enclosure s Safety Cord wired configured and screwed back into the Enclosure The Indoor Lower Dome is then snapped on The Surveyor99 rests o...

Страница 24: ...he Strain Relief Fitting must be cut off and re terminated after passing the cable through It is recommended to pass any RJ 45 Connectors through the fitting first BNC type connectors do not fit throu...

Страница 25: ...Supply Board at the proper block frames 8 Install the Video BNC cable connector to the Communication Power Supply Board s mating BNC Connector at location J1 9 Plug in all RJ 45 cable connectors to t...

Страница 26: ...rews with their mating standoffs and insert the Camera Drive into the Enclosure When seated tighten the 3 Captive Screws 14 Lift the Lower Dome up to the Surveyor99 and line up the 2 molded tabs on th...

Страница 27: ...upplied cable and Termination Box in this situation Detailed installation instructions will follow The ceiling material must provide a surface of suitable strength for the Surveyor99 weight of 4 5 lb...

Страница 28: ...strip approximately 0 25 inches 6 mm of insulation off of each individual wire c Make all connections to Terminal Blocks TB1 and TB3 with reference to Table 1 On TB3 the COMMAND IN CI and COMMAND IN C...

Страница 29: ...tion and address DIP Switches as follows a If RS 422 Mode will be used 1 Set switches 1 8 on DIP Switch 1 S1 to Surveyor99 s address as specified in Table 2 All addresses between 0 and 255 are valid a...

Страница 30: ...fect Vicoax protocol operation 4 Set switch 4 on DIP Switch 2 S2 to either position as it does not affect Vicoax protocol operation NOTE DIP Switches labeled ON or CLOSED and OFF or OPEN have the same...

Страница 31: ...e ceiling hole from the top Press the Mounting Ring Assembly down so the tabs are firmly seated into the material s cross section 3 Press the provided Nails through the Tab holes and into the ceiling...

Страница 32: ...le strength for the Housing and the Surveyor99 weight of 6 0 lb 2 7 kg 1 Install the Mount in accordance with the Installation Manual included with the Mount or prepare the vertical 1 0 inch NPT Pipe...

Страница 33: ...o the Communication Power Supply Board at the proper block frames 10 Install the Video BNC cable connector to the Communication Power Supply Board s mating BNC Connector at location J1 11 Plug in all...

Страница 34: ...ockwise looking up until the arrow on the Installation Label is aligned with the arrow on the inside of the Housing as shown in Figures 21c and 21d 17 Push the Surveyor99 straight up into the Housing...

Страница 35: ...supplied cable is limited to 8 feet 2 4 m the Termination Box must be mounted within the immediate area of the Surveyor99 The Mount must provide a support of suitable strength for the Sunshield Housi...

Страница 36: ...te the video coaxial cable with a BNC type male connector e Terminate the 8 conductor alarm cable or communication relay cable with an RJ 45 male connector if connectors J2 or J3 will be used WARNING...

Страница 37: ...ng 17 Turn the Surveyor99 counterclockwise looking up until the arrow on the Installation Label is aligned with the arrow on the inside of the Housing as shown in Figures 24b and 24c 18 Push the Surve...

Страница 38: ...28 Installation XX002 Rev 799 Surveyor99 Dome System NOTES...

Страница 39: ...d do not have a tri state high impedance state The RS 485 protocol is used for multiple Camera Domes in a daisy chain configuration RS 485 signals are not always active and do have a tri state high im...

Страница 40: ...EN NORMALLY OPEN NO ACTIVE LOW CLOSED The active state can be programmed through the Surveyor99 menu system These signals are connected to RJ 45 Connector J3 Alarm signals can be programmed for their...

Страница 41: ...tors do not fit through the fitting and must be terminated later NOTE If conduit pipe is not used the supplied Strain Relief Fitting must be installed in place of the one installed to provide sufficie...

Страница 42: ...t be just long enough to permit the Safety Cord to be the sole support of the Surveyor99 when removed from the Housing and just short enough to prevent improper bunching of the cables when installing...

Страница 43: ...J3 WARNING Failure to insert the RJ 45 Connectors into the correct mating connectors can cause damage to the Communication Power Supply Board upon power up 9 Place each cable into the Enclosure s Cabl...

Страница 44: ...k will resemble Figure 31 Feed the Control Cable into one of the sides and connect each wire to the appropriate screws Figure 31 is shown wired for typical Surveyor99 duplex operation with no relay NO...

Страница 45: ...behind the remaining wires to prevent it from touching other terminals 4 Feed the Control Cable from the Control Unit CPU or previous Surveyor99 into one of the sides of the Termination Box and conne...

Страница 46: ...the Termination Box must be mounted within the vicinity of the Surveyor99 Use of this kit is similar to the Accessory Kit The Termination Box provides a convenient connection from open wires to open...

Страница 47: ...BLOCK POWER TB1 TB1 1 H Hot TB1 2 N Neutral TB1 3 No connection RJ 45 ALARM J2 J2 1 ALARM1 Alarm input 1 J2 2 VSSA Ground J2 3 ALARM2 Alarm input 2 J2 4 VSSA Ground J2 5 ALARM3 Alarm input 3 J2 6 VSSA...

Страница 48: ...38 Wiring XX002 Rev 799 Surveyor99 Dome System NOTES...

Страница 49: ...e protocol mode setting RS 485 ON or RS 422 OFF Each switch is numbered from 1 to 8 and marked to indicate the ON position Surveyor99 will automatically detect the system s baud rate and will support...

Страница 50: ...X X 40 X X 126 X X X X X X 212 X X X X 41 X X X 127 X X X X X X X 213 X X X X X 42 X X X 128 X 214 X X X X X 43 X X X X 129 X X 215 X X X X X X 44 X X X 130 X X 216 X X X X 45 X X X X 131 X X X 217 X...

Страница 51: ...Surveyor99 for details on how to access the jumper sockets The 3 jumpers are included with each Surveyor99 but NOT INSTALLED at the factory There are 2 possible configurations as follows JUMPERS INSTA...

Страница 52: ...42 Configuration XX002 Rev 799 Surveyor99 Dome System NOTES...

Страница 53: ...amera Drive and lower it from the ceiling It will hang from the Safety Cord Refer to Figure 38 3 If it is necessary to completely remove the Camera Drive disconnect the Safety Cord Clip and all cables...

Страница 54: ...44 Disassembling the Surveyor99 XX002 Rev 799 Surveyor99 Dome System NOTES...

Страница 55: ...ed in accordance with this manual 3 Switch the AC power on to the Surveyor99 The monitor will display the power up test screen Figure 40 for the duration of its initial testing This test displays the...

Страница 56: ...D display remains with the number 94 and the monitor displays the Surveyor99 Main Menu as shown in Figure 42 5 Set up the Surveyor99 as desired using the remote keypad Proper operation has been verifi...

Страница 57: ...t as stated in Table 6 of the Technical Information Section If 22 to 34 VAC is measured return the Surveyor99 back to factory for service in accordance with the Shipping Instructions Section of this m...

Страница 58: ...48 Operation XX002 Rev 799 Surveyor99 Dome System NOTES...

Страница 59: ...and gently wipe the surface from the inside to the outer edge Then rinse with clean water and dry with clean dry pressurized air 5 Clean the Lower Dome s exterior with any soft cleaning cloth and a mi...

Страница 60: ...50 Maintenance XX002 Rev 799 Surveyor99 Dome System NOTES...

Страница 61: ...in Europe contact Vicon Industries U K Ltd Brunel Way Fareham PO15 5TX United Kingdom Phone 44 0 1489 566300 Fax 44 0 1489 566322 2 Attach a sheet of paper to the unit with the following information a...

Страница 62: ...52 Shipping Instructions XX002 Rev 799 Surveyor99 Dome System NOTES...

Страница 63: ...mmonly used cable types are RG 59 U and RG 11 U Each is actually a family of cables with widely varying electrical characteristics some of which are not suitable for CCTV applications Choose a cable t...

Страница 64: ...ir is also a suitable cable Choose a Belden cable type by referring to the characteristics and maximum distances listed below The maximum distance for the most reliable digital control refers to the d...

Страница 65: ...Current Indoor 1 2 A nominal Outdoor 2 0 A heater included Power Consumption Indoor 28 8 W nominal Outdoor 48 0 W nominal heater included Heat Equivalent Indoor 1 6 btu min 0 4 cal min Outdoor 2 7 btu...

Страница 66: ...positions alarm acknowledgement alarm or preset dwell times auxiliary function activation calling autotours tour repeat or chaining tours Autotour Capabilities 2 autotours available with 360 pan tilt...

Страница 67: ...play On screen menu driven system allowing full configuration of the Surveyor99 Screen Titling Capabilities Programmable for Camera Preset Sector and Alarms Fixed for Auxiliary Function and Lens statu...

Страница 68: ...9 CC 2 6725 04 Indoor Color NTSC Ceiling 22x Color SURV99 CC 1C 6484 01 Indoor Color PAL Ceiling 16x Color SURV99 MP 1 6485 00 Indoor Monochrome EIA Pendant 16x Color SURV99 MP 1C 6485 01 Indoor Monoc...

Страница 69: ...1207 Atlanta Office 3070AA Business Park Drive Norcross Georgia 30071 770 449 0499 800 824 8479 Fax 770 446 8779 Vicon U K Brunel Way Fareham PO15 5TX United Kingdom 44 0 1489 566300 Fax 44 0 1489 566...

Отзывы: