NetSure™ 2100 Series -48 VDC Power System Installation Manual (IM582138000)
|
Rev. C
14
•
Clearance requirements are (cabinet or wall mounting):
-
Minimum clearance is one inch from the face of the rectifier modules and one inch from the surface
of the rear sheet metal (for ventilation only; operation, installation and maintenance require more
clearance).
-
The system may also be mounted horizontally or vertically. Vertical mounting can be with the
distribution located at the top of the unit orientation or at the bottom of the unit orientation.
Securing the Relay Rack to the Floor (if furnished)
Secure the relay rack to the floor per site requirements. Refer to “General Requirements” on page 13.
Ventilation Requirements
Refer to “General Requirements” on page 13.
Relay Rack Floor Mounting Dimensions