Vertiv
|
NetSure™ 2100 Series -48 VDC Power System Installation Manual (IM582138000)
|
Rev. C
56
Figure 32:
Alarm Wiring to Battery Disconnect Circuit Breakers when Two (2) Battery Cabinets are Used
Note: Maximum of two (2) battery
disconnect circuit breakers.
Yellow Jumper/Alarm
Cable (P/N 545696)
(Supplied with
battery cabinet.)
Remove faston tab first,
then splice wire to the
blue/white wire of shelf
alarm cable P/N 565286.
Remove faston tab first,
then splice wire to the
orange/white wire of shelf
alarm cable P/N 565286.
Insulate and tie back
all unused wires of
cable P/N 545696.
Orange Jumper/Alarm
Cable (P/N 565513)
(Supplied with
battery cabinet.)
Insulate and tie back
all unused wires of
cable P/N 565513.
1st BATTERY CABINET
BATTERY DISCONNECT
CIRCUIT BREAKER
2nd BATTERY CABINET
BATTERY DISCONNECT
CIRCUIT BREAKER
Alarm Wiring to Battery Disconnect Circuit
Breakers when Two (2) Battery Cabinets are Used
Procedure
1. Remove resistor faston tab from circuit breaker
“NC” terminal on each battery disconnect.
2. Connect an ORANGE wire of alarm cable P/N
565513 to each circuit breaker “NC” alarm terminal.
Remove faston tab from alarm cable P/N 565513
and splice end to ORANGE/WHITE wire of alarm
cable P/N 565286. Note splice and sleeving
included in 565286. Insulate and tie back all unused
wires of alarm cable P/N 565513.
3. Connect a Yellow wire of alarm cable P/N
545696 to each circuit breaker “C” alarm terminal.
Remove faston tab from alarm cable P/N 545696
and splice end to BLUE/WHITE wire of alarm cable
P/N 565286. Note splice and sleeving included in
565286. Insulate and tie back all unused wires of
alarm cable P/N 545696.
4. There is NO connection to the circuit breaker
“NO (Normally Open)” alarm terminal.