IG-322-EN version 03; 22/07/2022
3
General instructions
SF
6
-insulated circuit-breaker panel:
Type
gae
.630 -1LSV(G)-/5/
in modular extensible design up to 24 kV, 20 kA
Contents
In view of the constant evolution in standards and design, the characteristics of the elements contained in this manual are subject
to change without prior notice. These characteristics, as well as the availability of components, are subject to confirmation by
Ormazabal
.
CAUTION!
When medium-voltage equipment is operating, certain components are live, other parts may be in movement and some may
reach high temperatures. Therefore, the use of this equipment poses electrical, mechanical and thermal risks.
In order to ensure an acceptable level of protection for people and property, and in compliance with applicable environmental
recommendations,
Ormazabal
designs and manufactures its products according to the principle of integrated safety, based on
the following criteria:
• Elimination of hazards wherever possible.
• Where elimination of hazards is neither technically nor economically feasible, appropriate protection functions are
incorporated in the equipment.
• Communication about remaining risks to facilitate the design of operating procedures which prevent such risks,
training for the personnel in charge of the equipment, and the use of suitable personal protective equipment.
• Use of recyclable materials and establishment of procedures for the disposal of equipment and components so
that once the end of their service lives is reached, they are duly processed in accordance, as far as possible, with the
environmental restrictions established by the competent authorities.
Consequently, the equipment to which the present manual refers complies with the requirements of section 11.2 of Standard
IEC 62271-1. It must therefore only be operated by appropriately qualified and supervised personnel, in accordance with the
requirements of standard EN 50110-1 on the safety of electrical installations and standard EN 50110-2 on activities in or near
electrical installations. Personnel must be fully familiar with the instructions and warnings contained in this manual and in other
recommendations of a more general nature which are applicable to the situation according to current legislation
[1]
.
The above must be carefully observed, as the correct and safe operation of this equipment depends not only on its design but also
on general circumstances which are in general beyond the control and responsibility of the manufacturer. More specifically:
• The equipment must be handled and transported appropriately from the factory to the place of installation.
• All intermediate storage should occur in conditions which do not alter or damage the characteristics of the equipment
or its essential components.
• Service conditions must be compatible with the equipment rating.
• The equipment must be operated strictly in accordance with the instructions given in the manual, and the applicable
operating and safety principles must be clearly understood.
• Maintenance should be performed properly, taking into account the actual service and environmental conditions in
the place of installation.
The manufacturer declines all liability for any significant indirect damages resulting from violation of the guarantee, under any
jurisdiction, including loss of income, stoppages and costs resulting from repair or replacement of parts.
Warranty
The manufacturer guarantees this product against any defect in materials and operation during the contractual period. In the
event that defects are detected, the manufacturer may opt either to repair or replace the equipment. Improper handling of this
equipment and its repair by the user shall constitute a violation of the guarantee.
Registered Trademarks and Copyrights
All registered trademarks cited in this document are the property of their respective owners. The intellectual property of this manual
belongs to
Ormazabal
.
[1]
For example, in Spain the “Regulation on technical conditions and guarantees for safety in high-voltage electrical installations” – Royal Decree
337/2014 is obligatory.
Contents
1. General........................................................................8
Liability and warranty . . . . . . . . . . . . . . . . . . . . . . . .8
Service information . . . . . . . . . . . . . . . . . . . . . . . . . .8
2. Safety regulations ......................................................9
Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Explanation of symbols and notes . . . . . . . . . . .10
General health and safety instructions . . . . . . .10
2.3.1. Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
2.3.2. Safety features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
2.3.3. Auxiliary device for operation,
maintenance and repair . . . . . . . . . . . . . . . . . . . . .11
2.3.4. Statutory health and safety instructions . . . . .11
2.3.5. Personal Protective Equipment (PPE) . . . . . . . .11
3. Transport and installation .......................................12
Safety notes for transport . . . . . . . . . . . . . . . . . . .12
Transport and unloading . . . . . . . . . . . . . . . . . . . .12
Arrival and unpacking. . . . . . . . . . . . . . . . . . . . . . .13
3.4. Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Installation and assembly . . . . . . . . . . . . . . . . . . .15
Planning of installation. . . . . . . . . . . . . . . . . . . . . .16
3.6.1. Floor fastening measurements . . . . . . . . . . . . . .16
3.6.2. Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
3.6.3. Possible installations . . . . . . . . . . . . . . . . . . . . . . . .19
Installation of the supply line for
the auxiliary and control circuits . . . . . . . . . . . . .20
Connection of the power cables . . . . . . . . . . . . .21
3.8.1. Optional VTs at the cable compartment. . . . . .22
3.9. Attachments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
3.10. Earthing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
4. Technical description ...............................................24
Circuit-breaker panel. . . . . . . . . . . . . . . . . . . . . . . .24
Extension of the circuit- breaker panel . . . . . . .25
Gas tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Pressure indicator . . . . . . . . . . . . . . . . . . . . . . . . . . .26
4.4.1. Checking the switching readiness . . . . . . . . . . .27
Density monitor (optional) . . . . . . . . . . . . . . . . . .28
4.5.1. Checking the switching readiness . . . . . . . . . . .28
Vacuum circuit-breaker. . . . . . . . . . . . . . . . . . . . . .29
Three-position switch . . . . . . . . . . . . . . . . . . . . . . .31
Three-position switch drive . . . . . . . . . . . . . . . . .32
Switch panel interlocks. . . . . . . . . . . . . . . . . . . . . .32
4.10. Current transformer. . . . . . . . . . . . . . . . . . . . . . . . .33
4.11. Voltage transformer. . . . . . . . . . . . . . . . . . . . . . . . .34
4.11.1. Voltage transformer connected
to the bus bar. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
4.11.2. Voltage transformer connected
to the outgoing . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
4.12. Capacitive voltage detecting system. . . . . . . . .35
4.13. Short-circuit indicator / earth fault
indicator (option). . . . . . . . . . . . . . . . . . . . . . . . . . .35
5. Operation..................................................................36
Switching accessories . . . . . . . . . . . . . . . . . . . . . . .36
Padlocking facility . . . . . . . . . . . . . . . . . . . . . . . . . .37
Delivery state of the circuit-breaker panel. . . .37
Switching the circuit-breaker panel . . . . . . . . . .40
5.4.1. Inspection activities and
safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . .40
5.4.2. Tensioning the spring accumulator . . . . . . . . . .41
5.4.3. Switching the circuit-breaker panel ON . . . . . .42
5.4.4. Switching the circuit-breaker panel OFF . . . . .47
6. Commissioning ........................................................51
safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . .51
Switching the circuit-breaker panel
(manually) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Undervoltage release (optional) . . . . . . . . . . . . .52
Switching using motor drive (option) . . . . . . . .52
Checking for electrical isolation . . . . . . . . . . . . .53
Cable test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
7. Maintenance .............................................................54
7.1. General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Inspection and maintenance . . . . . . . . . . . . . . . .55
7.2.1. Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
7.2.2. Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
7.2.3. Cleaning the circuit-breaker panel . . . . . . . . . . .56
7.2.4. Scope of maintenance on the vacuum
circuit-breaker’s mechanical drive groups . . . .56
circuit-breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
Return of switchgear . . . . . . . . . . . . . . . . . . . . . . . .57