IG-322-EN version 03; 22/07/2022
16
Transport and installation
General instructions
SF
6
-insulated circuit-breaker panel:
Type
gae
.630 -1LSV(G)-/5/
in modular extensible design up to 24 kV, 20 kA
3.6. Planning of installation
3.6.1. Floor fastening measurements
Figure 3.4 shows the floor mounting and the floor
breakthrough dimensions for the standard circuit-breaker
panel. On the left, the pressure relief into the cable pit, on
the right, with the rear pressure absorber channel into the
switchgear room.
Fastening bores Ø 12
Floor contact area
Floor opening
Only
gae
.630-1LSV-/5/ with deeper front cover for double cable
connection (optional)
Figure 3.4.
Dimensions in mm
Figure 3.5 shows the floor mounting and the floor
breakthrough dimensions for the circuit-breaker panel with
deep cable compartment cover. On the left, the pressure
relief into the cable pit, on the right, with the rear pressure
absorber channel into the switchgear room.
Fastening bores Ø 12
Floor contact area
Floor opening
Outgoing cable (Ø 70)
Earthing standard (Ø 30)
Earthing bus bar (Ø 70)
Figure 3.5.
Dimensions in mm