IG-322-EN version 03; 22/07/2022
15
General instructions
SF
6
-insulated circuit-breaker panel:
Type
gae
.630 -1LSV(G)-/5/
in modular extensible design up to 24 kV, 20 kA
Transport and installation
3.5. Installation and assembly
To install the circuit-breaker panel, use the installation plan
shown in Chapter 3.6.1. In order to assure secure standing
of the circuit-breaker panel use all fastening bores provided.
The depths of the individual panel types in the
gae
family
vary.
In order to ensure all possible block/ panel combinations
can be installed, the foundation projection must be drawn
at a distance of 135 mm from the wall!
On the variant with pressure absorber channel the minimum
distance is 100 mm.
If it is certain that during a system extension no:
•
gae
.630 -1LSFxx- panels
•
gae
measuring panels with metal cooling stretch are
installed, the distance from the wall can be reduced
to 100 mm.
To ease the assembly of the modular switchgear
gae
.630,
we recommend the following distances from side walls on
installation from left to right:
• Distance from left wall at least 100 mm
• Right wall distance at least 300 mm.
When installing from right to left the lateral wall distances
are reversed.
The area for the floor opening must not be reduced in
size, so that, in case of an arc incident, the hot gases
can be safely discharged.
A straight and level floor surface is a prerequisite for the
stress-free installation. Pay attention to the information
in DIN 43661. In particular the tolerance on the evenness
(maximum 1 mm over a measured length of 1 m) and
the tolerance on the straightness (maximum 1 mm per
metre and maximum 2 mm over the entire length of the
foundation rail) are to be observed.
To ease the assembly work on the installation of
several
gae
panels, we recommend the usage of a
metal chassis.
The fastening material is not part of the delivery.
To fastening the switch panel to a raised floor, we
recommend the following fastening material:
• Hexagon screw M10 (minimum M8, strength class 5.6)
DIN EN ISO 4017
• Washers DIN EN ISO 7093 (switch panel side)
• Washers DIN EN ISO 7089/7090 (raised floor side) or
tapered washers for fastening to U-sections
• Spring lock ring DIN 127 / DIN 128
• Hexagon nut M10 DIN EN ISO 4032
In the case of installation on concrete with a strength of
B ≥ 25 N/mm², we recommend the following fastening
material:
• Fischer plastic dowels of type S12
• Wood screw DIN 571-10x80-St
• Washer DIN 125 A10
To make the fastening bores accessible for installation,
remove the front cover (see Chapter 5) and if applicable the
cable fixing irons of cable connection compartment.