IG-322-EN version 03; 22/07/2022
14
Transport and installation
General instructions
SF
6
-insulated circuit-breaker panel:
Type
gae
.630 -1LSV(G)-/5/
in modular extensible design up to 24 kV, 20 kA
After moving the circuit-breaker panel to the place of
installation, remove the lifting eyes.
When installing as an end panel, close off the thread with a
flexible plastic plug.
Keep the eyebolts in a safe, accessible place for future use in
transporting the circuit-breaker panel. When re-fitting the
eyebolts, it must be observed that they are tightly seated
and in the correct position.
Check the circuit-breaker panel delivery for correctness and
completeness. The serial numbers on the delivery note and
on the rating plate on the circuit-breaker panel (Figure 3.3)
must match.
1
Serial number
2
Technical data
3
Standards applied
4
Document number
5
Type of unit
6
Manufacturing date: month/year
Figure 3.3.
Rating plate (example)
3.4. Storage
In the factory the circuit-breaker panel is packed ready for
transport and storage. It must only be stored in dry, clean
rooms and must be protected against excessive soiling.
The environmental conditions must comply with
IEC 62271-1 / DIN EN 62271-1 and VDE 0671-1, ambient
temperature class “minus 5 indoor”.