IG-322-EN version 03; 22/07/2022
27
General instructions
SF
6
-insulated circuit-breaker panel:
Type
gae
.630 -1LSV(G)-/5/
in modular extensible design up to 24 kV, 20 kA
Technical description
4.4.1. Checking the switching readiness
Danger to life due to arc fault!
The gas filling pressure must be checked prior to each
switching operation!
Read the switching readiness of the switch panel depending
on the gas filling pressure and temperature on the pressure
indicator (Tab. 4.1).
Reading
ching readiness of the switch panel
Case 1
0,6 bar
-25°
C
0°C
+20°
C
+40°
C
12258533 11 15
Indicator completely within the green range
Ready for switching
Case 2
0,6 bar
-25°
C
0°C
+20°
C
+40°
C
12258533 11 16
Indicator within the range of the temperature
compensation curve
=> Measure the temperature (T) of the switchgear
room and read as follows:
–
Case 2A: Intersection of indicator and temperature
ring within the green range (below the temperature
compensation curve)
e.g. for T=+10°C
Ready for switching
Case 2B: Intersection of indicator and temperature
ring within the red range (above the temperature
compensation curve)
e.g. for T=+20°C
NOT ready for switching
(Contact customer service)
Case 3
0,6 bar
-25°
C
0°C
+20°
C
+40°
C
12258533 11 17
Indicator at left end stop
NOT ready for switching
(Contact customer service)
Table 4.1.