IG-322-EN version 03; 22/07/2022
13
General instructions
SF
6
-insulated circuit-breaker panel:
Type
gae
.630 -1LSV(G)-/5/
in modular extensible design up to 24 kV, 20 kA
Transport and installation
3.3. Arrival and unpacking
The goods must be checked immediately upon receipt!
Any complaints have to be stated on the freight
document and countersigned by the driver!
In case of complaints please contact your distributor:
www.ormazabal.com
Remove the tightening straps. The circuit-breaker panel
is then no longer secured. Due to its design, the centre
of gravity of the circuit-breaker panel is higher than the
middle of the switch panel.
When handling the circuit- breaker panel in unsecured
condition the unit may tip over! Particular attention is
to be paid to this issue when transporting the circuit-
breaker panel to its place of installation. It not allowed
to use levers to transport the circuit-breaker panel to
its final position. This action could cause damage to
the enclosure.
Eyebolts are fitted to both sides of the
gae
.630 -1LSV panel,
which hold the panel safely in its position of centre of
gravity when transporting with chain or rope lifting gear
(Figure 3.2). Only transport cross members must be used
with this type of lifting gear. Otherwise there is a risk of
damage to the panel.
In some individual cases, the eyebolts are enclosed with the
panel. When fitting the eyebolts, it must be observed that
they are tightly seated and in the correct Figure 3.2 position.
37250305
Figure 3.2.