General instructions
SF
6
-insulated circuit-breaker panel:
Type
gae
.630 -1LSV(G)-/5/
in modular extensible design up to 24 kV, 20 kA
Operation
5.4.4. Switching the circuit-breaker panel OFF
To switch the circuit-breaker panel OFF, proceed as follows:
Use the capacitive voltage detection system to check
whether voltage is indicated for phases L1, L2 and L3
(see Chapter 6.5).
1.
Switch position with activated disconnector and
deactivated earthing switch ("Figure 5.22."), circuit-
breaker switched ON and relaxed spring accumulator
Figure 5.22.
Figure 5.23.