7. Maintenance
7.1. General
Maintenance, repair work and subsequent
modifications must only be performed by skilled
personnel and in compliance with the operating
instructions, the accident prevention instructions and
the regulations of the liability associations.
Maintenance is used to ensure continuing trouble-free
operation and the longest possible service lifetime of the
switching device and the equipment integrated. It covers
the following, closely related areas in accordance with
DIN 31051 respectively:
•
Inspection:
Determination of the actual state
•
Maintenance:
Measures to preserve the nominal state (ensuring
trouble-free function)
•
Repair:
Measures to restore the nominal state.
The circuit-breaker panel is low- maintenance.
The gas tank is welded gas-tight and all components inside
are maintenance- free.
The SF
6
gas is resistant to ageing and is not consumed
during the switching operations.
Under normal conditions, the gas charge does not need to
be replaced during the operational life of the circuit-breaker
panel.
The vacuum circuit-breakers feature a simple and robust
design.
They have a long life expectancy. Their drives are low
maintenance and the vacuum contact chambers are
maintenance-free for their entire service lifetime.
Even frequent switching of operating and short-circuit
currents will not degrade the vacuum.
The maintenance intervals for the mechanical assembly
on the vacuum circuit-breaker are defined by the ambient
conditions, operating frequency and number of short
circuit breaks.