SD710 Series Servo Drive User Manual Chapter 5 Commissioning and Operation
20
●
If the setting is set to the pulse deviation clear state, the servo lock function is disabled. In this
case, the servo motor will rotate slightly due to the drift pulse in the speed loop.
●
When the position mode is running, the servo motor stops running due to the travel limit, and
the position deviation remains. Pay attention to the motor action safety when removing the travel
limit.
Wiring for Pulse Deviation Clearance
The pulse deviation clear signal is a universal configurable switch input, see
"Multi-function CN1 terminal wiring"
for wiring
details.
5.2.7 Command Pulse Disable
The command pulse disable (INHIBIT) function is a function that disables command pulse input counting during position
control. When this function is active, the servo unit enters a state where command pulse input cannot be received.
(1) Configuration of command pulse prohibition
This signal is not configured in the factory default switch configuration, so you need to configure the pin number for this
function(0x0D) by parameters Pn601 to Pn609.
Related input terminal
Setting
Symbol
Function
name
Instructions
Trigger
method
Running
mode
0x0D
INHIBIT
Command
pulse disable
This signal is used to control the drive
from receiving further pulse commands.
Valid: disables receiving pulse
commands and stops counting.
Invalid: allows the pulse command to be
received and counted.
Voltage
level
trigger
□
P
□
S
□
T
(2) Wiring for Command Pulse Prohibition
The command pulse disable signal is a universal configurable switch input, see
"Multi-function CN1 terminal wiring"
wiring details.
5.2.8 Positioning Proximity
In positioning proximity (NEAR) position control, the host computer can receive the positioning proximity signal before
confirming the positioning completion signal to prepare for the sequence of actions after positioning completion. In this
way, the time required for action at positioning completion can be shortened. This signal is usually used in pairs with the
positioning completion signal, see
for details on positioning completion signals.
(1) Configuration for Positioning Proximity
This signal is not configured in the factory default switch output configuration, so you need to configure the pin number
for this function (0x08) by parameters Pn611 to Pn614.
Related output terminal
Setting
Symbol
Function name
Instructions
Trigger
method
Running
mode
!