Section 11 - Setup Menu
MC032 - MCP-25 Control
Pressure-
Transducer
Configuration
Parameters
Nr
Nr
Nr
Nr
Nr—Pressure transducer number (1-2)
M
M
M
M
M—Pressure transducer mode
0 = Percentage pressure curve. Pressure data entered in %
(0-100%)
1 = Same as mode 0 with a bypass function. T-bypass and V-
bypass are programmed in this
mode. (A bypass card is required.)
2 = Same as mode 0 but with a different bypass function. A
bypass card is also required.
t-bypass
t-bypass
t-bypass
t-bypass
t-bypass—Used only in mode 1. The length of time that the bypass
valve remains open when activated (0-10 seconds).
V-bypass
V-bypass
V-bypass
V-bypass
V-bypass—
Mode 1—If parent machine is decelerating and speed drops under V-
bypass, the valve opens for the time t-bypass. The valve can only
be activated again if the machine speed is increased to higher
than the threshhold speed (V-bypass).
Mode 2—The valve opens if the parent machine speed is higher than
V-bypass and closes if the speed drops lower than V-bypass (t-
bypass has no effect).
LF
LF
LF
LF
LF—Calibration factor. The calibration factor (LF) is used to
compensate for differences between the hardware (I/O board)
and the software. This value is factory set and should require no
further adjustment. If an I/O board is replaced, make sure that the
LF values in this menu correspond with the LF values printed on
the new I/O board.
V-Bypass
Speed
Time