X5 AC Drive User’s Manual
X5 Parameter Summary Table
DPD00089A
-
iv -
© 2009 Vacon Incorporated All Rights Reserved
207
Vin1 Span
10.0% to 200.0%
100.00%
208
Cin Config
text string
0-20mA 50
209
Cin Offset
0.0% to 100.0%
0.0%
210
Cin Span
10.0% to 200.0%
100.0%
211
Vin2 Config
text string
0-10V
212
Vin2 Offset
0.0% to 100.0 %
0.00%
213
Vin2 Span
10.0% to 200.0%
100.00%
214
Vin1 Filter Time
0 to 1000 ms
20 ms
215
Cin Filter Time
0 to 1000 ms
20 ms
216
Vin2 Filter Time
0 to 1000 ms
20 ms
217
Trim Ref Enable (Set k-Factor)
text string
0
218
Trim % Factor
-100.0 - 100.0%
0.0%
222
Ref Loss Config
text string
No Fault
301
Min Frequency
0.0 - Max Freq.
0.0 Hz
302
Max Frequency
20.0 - 400.0 Hz
60.0 Hz
303
Preset Freq 1
Min Freq-Max Freq
5.0 Hz
304
Preset Freq 2
Min Freq-Max Freq
10.0 Hz
305
Preset Freq 3
Min Freq-Max Freq
20.0 Hz
306
Preset Freq 4
Min Freq-Max Freq
30.0 Hz
307
Preset Freq 5
Min Freq-Max Freq
40.0 Hz
308
Preset Freq 6
Min Freq-Max Freq
50.0 Hz
309
Cut-off Freq
0.0 - 5.0 Hz
0.0 Hz
310
Preset Freq 7
Min Freq-Max Freq
60.0 Hz
311
Preset Freq 8
Min Freq-Max Freq
0.0 Hz
312
Preset Freq 9
Min Freq-Max Freq
2.5 Hz
313
Preset Freq 10
Min Freq-Max Freq
7.5 Hz
314
Preset Freq 11
Min Freq-Max Freq
15.0 Hz
315
Preset Freq 12
Min Freq-Max Freq
25.0 Hz
316
Preset Freq 13
Min Freq-Max Freq
35.0 Hz
317
Preset Freq 14
Min Freq-Max Freq
45.0 Hz
318
Preset Freq 15
Min Freq-Max Freq
55.0 Hz
380
Keeper Input Cfg
text string
4 (disabled)
381
Keeper Max Scale
0-32000
1000
382
Keeper Save Time
00:00 - 23:59
0:00
384
Keeper Save Rate
text string
0 (24 hour)
385
Keeper Input Value
0-32000
Read-only
386
Keeper Time Rate
text string
1 (minute)
387
Keeper Rec. Num
0-255
Read-only
388
Active Kpr. Record
0-255
Read-only
389
Keeper Units
text string
1 (GPM)
401
Ramp Select
text string
ART-DI
402
Accel Time 1
0.1-3200.0 sec
5.0 sec
403
Decel Time 1
0.1-3200.0 sec
5.0 sec
404
Accel Time 2
0.1-3200.0 sec
3.0 sec
405
Decel Time 2
0.1-3200.0 sec
3.0 sec
406
DC Inject Config
text string
DC at Stop
407
DC Inject Time
0.0-5.0 sec
0.2 sec
408
DC Inject Level
0.0% to 100.0%
50.0%
409
DC Inj Freq
0.0 to 20.0 Hz
0.0 Hz
410
DB Config
text string
Internal
414
S Ramp Rounding
1 - 100%
25%
No.
Parameter Name
Options
Default
User Setting
See Page
= cannot change in Run
Bold type
= Level 1 parameter
Note that all parameters can be addressed by adding 40000 to the parameter number. For example, parameter 201 (Input Mode) can be
addressed by Modbus address 40201.