3.3 Dissipation Requirements
Table 3-1: Dissipation Requirements for X5 Models in Enclosures
(Page 1 of 2)
Model
Required Dissipation for Models Entirely Inside an Enclosure at
Rated Current, 3KHz Carrier Frequency (Watts)
X5C1S010C
47
X5C20010C
48
X5C20020C
71
X5C20030C
92
X5C20050C
132
X5C20075C
177
X5C20100C
263
X5C20150C
362
X5C20200C
550
X5C20250C
653
X5C20300C
779
X5C40010C
34
X5C40020C
48
X5C40030C
71
X5C40050C
91
X5C40075C
114
X5C40100C
155
X5C40150C
304
X5C40200C
393
X5C40250C
459
X5C40300C
458
X5C40400C
695
X5C40500C
834
X5C40600C
776
X5C40750C
988
X5C41000C
1638
X5C41250D
1656
X5C41500D
1891