X5 AC Drive User’s Manual
X5 Parameter Summary Table
DPD00089A
-
v -
© 2009 Vacon Incorporated All Rights Reserved
415
Accel Time 3
0.1-3200.0 sec
10.0 sec
416
Decel Time 3
0.1-3200.0 sec
10.0 sec
417
Accel Time 4
0.1-3200.0 sec
15.0 sec
418
Decel Time 4
0.1-3200.0 sec
15.0 sec
490
App Macro
text string
Factory
491
Seq Appl
text string
Disabled
492
SIO Visible
text string
No
501
V/Hz Select
text string
Linear Fixed
502
Voltage Boost
0.0-50%
1.0%
503
V/Hz Knee Freq
25.0-400.0 Hz
60.0 Hz
504
Skip Freq Band
0.2-20.0 Hz
0.2 Hz
505
Skip Freq 1
Min Freq-Max Freq
0.0 Hz
506
Skip Freq 2
Min Freq-Max Freq
0.0 Hz
507
Skip Freq 3
Min Freq-Max Freq
0.0 Hz
508
Skip Freq 4
Min Freq-Max Freq
0.0 Hz
509
Rated Mtr Volt
100V-690V
Model dependent
510
Rated Mtr FLA
50% - 200% of ND Rating
ND Rating
511
Rated Mtr RPM
0-24000 rpm
1750 rpm
512
Midpoint Freq
0.0 Hz-V/Hz Knee Freq
60.0 Hz
513
Midpoint Volt
0.0-100.0%
100.0%
514
Motor RS
0.0-655.35 Ohms
Model dependent
515
Power Factor
0.50-1.00
0.80
516
Slip Comp Enable
text string
No
517
Single Phase
text string
No
519
Find Mtr Data
Not active / Motor RS
Not active
520
Filter FStator
1 - 100 ms
8 ms
521
Start Field En
text string
No
522
Filter Time Slip
10 - 1000 ms
100 ms
523
Id Percent
0 - 200%
Read-only
524
Iq Percent
0 - 200%
Read-only
525
Power Fail Config
text string
CTS No Msg
526
UV Ride-Thru En
text string
w/ LVT
600
Current Lim Sel
text string
0
601
Cur Lim Mtr Fwd
5%-150%
120%
602
Cur Lim Mtr Rev
5%-150%
120%
603
Cur Lim Reg Fwd
5%-150%
80%
604
Cur Lim Reg Rev
5%-150%
80%
605
Cur Lim Freq
0.0 - 400.0 Hz
3.0 Hz
606
Ramp Time CL
0.1-3200.0 sec
1.0 sec
607
Cur Limit Minimum
0 - 50%
10%
608
Restart Number
text string
0
609
Restart Delay
0-60 sec
60 sec
610
Timed OL Select
text string
0 (Std Ind 60s)
613
Max Regen Ramp
100 - 1000%
300%
614
Stability Gain
0 - 10
Model Dependent
615
Stability Rate
0 - 1000
Model Dependent
700
Vmet Config
text string
Freq Out
701
Vmet Span
0.0-200.0%
100.0%
702
Imet Config
text string
Drive Load
703
Imet Span
0.0-200.0%
100.0%
704
Imet Offset
0.0-90.0-%
0.0%
No.
Parameter Name
Options
Default
User Setting
See Page
= cannot change in Run
Bold type
= Level 1 parameter
Note that all parameters can be addressed by adding 40000 to the parameter number. For example, parameter 201 (Input Mode) can be
addressed by Modbus address 40201.