X5 AC Drive User’s Manual
Chapter 5: Operation and Programming
DPD00089A
-
46 -
© 2009 Vacon Incorporated All Rights Reserved
You can access
Program mode
is entered by stopping the drive and pressing the
Program
(PROG)
key for Level 1 access; or holding down
SHIFT
while pressing
PROG
for Level 2 access. Pressing
and holding the
Enter
key and then pressing the
Program
key will show only those parameters that
have been changed from the factory defaults. Table 5-2 describes the function of the keys in Program
mode.
Table 5-2: Function of Keys in Program Mode
Press this key to have the drive enter Program mode and have Level 1 parameters available. (To
access Level 2 parameters, hold down
SHIFT
while pressing this key; to access Macro mode, hold
down the
PROG
key for more than 3 seconds.) Once Program mode is active, pressing this key at
any time returns the drive to the Operation mode. If an Access Code has been programmed, it must
be entered to proceed with programming. See
811 (Access Code)
(
NOTE:
To see what parameters have changed from the factory default, press ENTER + PROG. If the display flashes
“Factory Defaults,” no parameters have changed.
In the Program mode, pressing this key scrolls
forward
through the parameters. If the P indicator is
flashing, it increases the value of the parameter. To change the scroll rate, hold the
SHIFT
key at
the same time to increase the scroll rate; release the
SHIFT
key to return to the normal scroll rate.
Press the
ENTER
key to store the new value.
In the Program mode, pressing this key scrolls
backward
through the parameters. If the P indicator
is flashing, it decreases the value of the parameter. To change the scroll rate, hold the
SHIFT
key
at the same time to increase the scroll rate; release the
SHIFT
key to return to the normal scroll rate.
Press the
ENTER
key to store the new value.
NOTE:
If the P indicator on the keypad display is flashing, momentarily pressing and releasing both the
INC
and
DEC
keys at the same time restores the parameter to the factory default value. Press
ENTER
to store the
new value.
the descriptions for the INC and DEC keys
to see how
they work with the SHIFT key.
This key must be pressed after the value of a parameter has been changed to store the new value.
The display will show “stored” for one second indicating that the new value has been entered into
memory.
NOTE:
The X5 unit allows you to view only those parameters that have changed. If you press keypad keys ENTER
and PROGram simultaneously, only those parameters that have been changed from the factory defaults will be
shown.
Table 5-3: Function of Keys in Fault Mode
In Fault mode, pressing the
INC
(up arrow) and
DEC
(down arrow) keys allows you to view the
drive’s status immediately before the fault occurred. Use the
INC
or
DEC
keys to scroll through
the status parameters. Press the
STOP
(Reset) key to return to normal operation.
“Chapter 8: Troubleshooting” on page 125
for information about viewing Advanced Fault
Codes and understanding error codes.
The red STOP indicator functions as a reset button when in Fault mode. If the drive has
stopped because of a fault, this light flashes to call attention to the display.