X5 AC Drive User’s Manual
X5 Parameter Summary Table
DPD00089A
-
vi -
© 2009 Vacon Incorporated All Rights Reserved
705
Relay 1 Select
text string
1 (Drv Fault)
706
Relay 2 Select
text string
2 (Drive Run)
707
DO1 Select
text string
0 (Drv Ready)
708
DO2 Select
text string
6 (At Speed)
719
Digital Input Filter Time
1-1000 msec
5 msec
720
Active Logic
text string
1 (Active High)
721
DI1 Configure
text string
0 (Preset 1)
722
DI2 Configure
text string
1 (Preset 2)
723
DI3 Configure
text string
2 (Preset 3)
724
DI4 Configure
text string
6 (Alt Ramp)
725
DI5 Configure
text string
7 (Fault Reset)
726
MOL Polarity
text string
1 (NO Operate)
727
MOL Configure
text string
21 (MOL)
740
Thres 1 Select
text string
9 (Load High)
741
Thres 1 High
-300.00 to 300.00%
100.00%
742
Thres 1 Low
-300.00 to 300.00%
0.00%
743
Thres 2 Select
text string
15 (Current High)
744
Thres 2 High
-300.00 to 300.00%
100.00%
745
Thres 2 Low
-300.00 to 300.00%
0.00%
746
Timer 1 Type
text string
0 (On Delay)
747
Timer 1 Signal
text string
1 (Drv Fault)
748
Timer 1 Time
0.0 - 320.0 sec
1.0 sec
749
Timer 2 Type
text string
0 (On Delay)
750
Timer 2 Signal
text string
1 (Drv Fault)
751
Timer 2 Time
0.0 - 320.0 sec
1.0 sec
794
Drive Name
text string
serial number
799
Config USB Mode
text string
0 (Disabled)
801
Program Number
0-9999
0
802
Start Options
text string
0 (LS Lockout)
803
PWM Frequency
0.6-16.0 kHz
3.0 kHz
804
Display Mode
text string
0 = Std Disply
805
Display Units
alphanumeric
0 (blank)
809
Display Scale
1-65535
18000
810
Language
text string
0 (English)
811
Access Code
0-9999
0
812
Freq Ref Output
text string
0 (6FS)
813
Speed Ratio
0.0-200.0%
100.0%
814
Display Status
text string
0 (Drive load)
816
Fly Catch Mode
text string
0 (Sweep FWD)
819
Flt Text #1
text string
User Flt 1
825
Flt Text #2
text string
User Flt 2
850
PID Configure
text string
0 (No PID)
851
PID FBk Config
text string
0 (Vin1)
852
PID Prop Gain
0-2000
0
853
PID Int Gain
0-10000
0
854
PID Feed Gain
0-2000
1000
855
PID Error 1
0.00-100.00%
Read-only
856
PID Error 2
0.00-100.00%
Read-only
857
PID High Corr
0.00-100.00%
100.00%
858
PID Low Corr
0.00-100.00%
0.00%
859
PID Deriv Gain
0-200
0.00%
No.
Parameter Name
Options
Default
User Setting
See Page
= cannot change in Run
Bold type
= Level
1
parameter
Note that all parameters can be addressed by adding 40000 to the parameter number. For example, parameter 201 (Input Mode) can be
addressed by Modbus address 40201.