X5 AC Drive User’s Manual
Chapter 7: X5 Parameters
DPD00089A
-
118 -
© 2009 Vacon Incorporated All Rights Reserved
1001
High Analog Voltage Threshold (Vin1) -
The active sequencer state lasts until the voltage signal
applied to terminal Vin1 is > a value programmed in “Seq Count X.” The value programmed in “Seq
Count X” should be the percentage of input after span and offset are applied (where 100.00% = 10000).
Note:
The % of analog input after span and offset can be read in
910, Vin1 Status
.
1010
Drive State (AND) -
With this selection, the count parameter represents a bit-packed status word
corresponding to drive state conditions. The format of this status word is documented in
on Drive State Conditions” on page 119
. The Sequencer will advance if
all
of the drive conditions are
met that are enabled in the count parameter.
1011
Drive State (OR) -
With this selection, the count parameter represents a bit-packed status word
corresponding to drive state conditions. The format of this status word is documented in
on Drive State Conditions” on page 119.
The Sequencer will advance if
any
of the drive conditions are
met that are enabled in the count parameter.
1100
Encoder Home Pulse -
The active sequencer state lasts until the no. of pulses programmed into “Seq
Count X” is detected on Encoder Home Input C+, C-. This allows advancement on process revolutions.
0111
1101
1110
1111
The sequencer will never advance if these options are selected.
Table 7-9: Seq Count Definition Based on Cntl Parameter Configuration
(Page 2 of 2)
Bits 6-9
of Seq
Cntl
Description of Seq Count Function
Содержание X5
Страница 1: ...X5 AC Drive user s manual ...
Страница 4: ......
Страница 125: ...X5 AC Drive User s Manual Chapter 7 X5 Parameters DPD00089A 123 2009 Vacon Incorporated All Rights Reserved ...
Страница 126: ...X5 AC Drive User s Manual Chapter 7 X5 Parameters DPD00089A 124 2009 Vacon Incorporated All Rights Reserved ...
Страница 138: ......
Страница 140: ......