X5 AC Drive User’s Manual
X5 Parameter Summary Table
DPD00089A
-
vii -
© 2009 Vacon Incorporated All Rights Reserved
860
PID Sleep Cfg
text string
0 (disabled)
861
PID Sleep Lvl
0.00-100.00%
0.00%
862
PID Wake-up Lvl
0.00-100.00%
100.00%
863
Sleep Delay Time
0.0-300.0 sec
0.0 sec
864
Wake-up Delay
0.0-300.0 sec
0.0 sec
865
PID Feedback
0.00-100.00%
Read-only
866
PID Reference
0.00-100.00%
Read-only
867
PID User Units
text string
0 (No)
880
FBus Read 1
0-65535
103
881
FBus Read 2
0-65535
104
882
FBus Read 3
0-65535
105
883
FBus Read 4
0-65535
107
884
FBus Read 5
0-65535
909
890
FBus Write 1
0-65535
907
891
FBus Write 2
0-65535
402
892
FBus Write 3
0-65535
403
893
FBus Write 4
0-65535
920
894
FBus Write 5
0-65535
921
900
SIO Protocol
text string
0 (RTU N81)
901
SIO Baud Rate
text string
2 (9600)
902
Comm Drop #
1-247
1
903
SIO Timer
0.0-60.0 sec
1.0 sec
904
SIO Cntl Word
Bit 0-15
0x0000
905
Ext Ref Freq1
Min-Max Freq
0.0 Hz
906
Ext Ref Freq2
Min-Max Freq
0.0 Hz
907
Cntl Word 2
Bit 0-15
0x0000
908
Status Word
Bit 0-15
Read-only
909
DI Status
Bit 0-14
Read-only
910
Vin1 Status
0.00-100.00%
Read-only
911
Cin Status
0.00-100.00%
Read-only
912
Vin2 Status
0.00-100.00%
Read-only
913
Output Status
Bit 0-5
Read-only
914
Vmet Status
0.00-100.00%
Read-only
915
Imet Status
0.00-100.00%
Read-only
916
Infrared Baud
text string
2 (9600)
917
FBus Port Config
text string
1 (485 w/ctl)
920
SIO Vmet Level
0.00-100.00%
100.00%
921
SIO Imet Level
0.00-100.00%
100.00%
926
Status Word 2
Bit 0-2
Read-only
930
Seq Cntl 1
Bit 0-15 (hex control)
0x0000
931
Seq Cntl 2
Bit 0-15 (hex control)
0x0000
932
Seq Cntl 3
Bit 0-15 (hex control)
0x0000
933
Seq Cntl 4
Bit 0-15 (hex control)
0x0000
934
Seq Cntl 5
Bit 0-15 (hex control)
0x0000
935
Seq Cntl 6
Bit 0-15 (hex control)
0x0000
936
Seq Cntl 7
Bit 0-15 (hex control)
0x0000
937
Seq Cntl 8
Bit 0-15 (hex control)
0x0000
938
Seq Cntl 9
Bit 0-15 (hex control)
0x0000
939
Seq Cntl 10
Bit 0-15 (hex control)
0x0000
940
Seq Cntl 11
Bit 0-15 (hex control)
0x0000
941
Seq Cntl 12
Bit 0-15 (hex control)
0x0000
942
Seq Cntl 13
Bit 0-15 (hex control)
0x0000
No.
Parameter Name
Options
Default
User Setting
See Page
= cannot change in Run
Bold type
= Level 1 parameter
Note that all parameters can be addressed by adding 40000 to the parameter number. For example, parameter 201 (Input Mode) can be
addressed by Modbus address 40201.