X5 AC Drive User’s Manual
Chapter 7: X5 Parameters
DPD00089A
-
74 -
© 2009 Vacon Incorporated All Rights Reserved
This parameter sets the starting time that the drive is enabled to run if a Run signal is active. If equal to “Time Run
Enable,” the function is disabled. (See
“Enabling the X5 Based on Time of Day (TOD)” on page 57
158 TOD Run Dis 2
12:00
Range: 00:00 - 23:59
Level: 2 (Clock)
This parameter sets the ending time that the drive is enabled to run if a Run signal is active. If equal to “Time Run
Disable,” the function is disabled. (See
“Enabling the X5 Based on Time of Day (TOD)” on page 57
.)
160 Weekend TOD Enable
12:00
Range: 00:00 - 23:59
Level: 2 (Clock)
This parameter sets the starting time that the drive is enabled to run if a Run signal is active. If equal to “Time Run
Enable,” the function is disabled. (See
“Enabling the X5 Based on Time of Day (TOD)” on page 57
162 Weekend TOD Dis
12:00
Range: 00:00 - 23:59
Level: 2 (Clock)
This parameter sets the ending time that the drive is enabled to run if a Run signal is active. If equal to “Time Run
Disable,” the function is disabled. (See
“Enabling the X5 Based on Time of Day (TOD)” on page 57
.)
171 Reminder 1 Conf.
Default = Disabled
Range: n/a
Level: 2
This parameter configures the reminder to measure the run time or total time before activating the reminder.
The following data values may be assigned to this parameter:
Parameter Value
Description
0
Disabled
1
Minute
2
Run Min
3
Gated Min
(See
for more information on using these parameters.)
172 Reminder 1 Time
1
Range: 1 - 32000 minutes
Level: 2
Based on parameter
176 (Reminder 2 ETA)
, this parameter sets the duration of time in minutes until reminder #1 is
for more information on using these parameters.)
173 Reminder 1 ETA
Read-only
Range: +/- 32000 minutes
Level: 2
This parameter displays the length of time until reminder #1 is set. (See
for more information
on using these parameters.)
174 Reminder 2 Conf.
Default = Disabled
Range: n/a
Level: 2
This parameter configures the reminder to measure the run time or total time before activating the reminder.
The following data values may be assigned to this parameter:
Parameter Value
Description
0
Disabled
1
Hour
2
Run Hour
3
Gated Hour
(See
for more information on using these parameters.)
175 Reminder 2 Time
1
Range: 1 - 32000 hours
Level: 2
Based on parameter
179 (Reminder 3 ETA)
, this parameter sets the duration of time in hours until reminder #2 is set.
(See
for more information on using these parameters.)
176 Reminder 2 ETA
Read-only
Range: +/- 32000 hours
Level: 2
Table 7-2: Description of X5 Parameters
(Page 4 of 40)
Содержание X5
Страница 1: ...X5 AC Drive user s manual ...
Страница 4: ......
Страница 125: ...X5 AC Drive User s Manual Chapter 7 X5 Parameters DPD00089A 123 2009 Vacon Incorporated All Rights Reserved ...
Страница 126: ...X5 AC Drive User s Manual Chapter 7 X5 Parameters DPD00089A 124 2009 Vacon Incorporated All Rights Reserved ...
Страница 138: ......
Страница 140: ......