X5 AC Drive User’s Manual
Chapter 4: Connections
DPD00089A
-
34 -
© 2009 Vacon Incorporated All Rights Reserved
Figure 4-2: Power Terminals on Higher-HP Models
4.4.2 Typical Power Connections
Section 4.3
starting on page 31 for input line requirements.
Note that when testing for a ground fault, do not short any motor lead (T1/U, T2/V, or T3/W) back
to an input phase (L1/R, L2/S, or L3/T).
It is necessary to provide fuses and a disconnect switch for the input AC line in accordance with all
applicable electrical codes. The X5 AC drive is able to withstand a 150% overload for 60 seconds
for heavy duty rating, and 120% overload for normal duty rating.
The fusing and input protection of the drive must always meet UL, NEC (National Electric Code),
and CEC (Canadian Electric Code) requirements. All fuse ratings included in
below are
for reference only and do not supersede code requirements. The recommended supplier is Bussman.
Table 4-6: Fuse Ratings
(Page 1 of 2)
Model Number
Fuse Size
115 Vac
JJS/JJN
Fuse Size
208 Vac
JJS/JJN
Fuse Size
230 Vac
JJS/JJN
Fuse Size
380 Vac
JJS
Fuse Size
460 Vac
JJS
Fuse Size
575 Vac
JJS
X5C1S010C
20
—
—
—
—
—
X5C20010C
—
10
6
—
—
—
X5C20020C
—
15
10
—
—
—
X5C20030C
—
20
15
—
—
—
X5C20050C
—
30
25
—
—
—
X5C20075C
—
40
35
—
—
—
X5C20100C
—
50
40
—
—
—
X5C20150C
—
70
60
—
—
—
X5C20200C
—
90
80
—
—
—
X5C20250C
—
100
90
—
—
—
X5C20300C
—
125
110
—
—
—