X5 AC Drive User’s Manual
Chapter 7: X5 Parameters
DPD00089A
-
95 -
© 2009 Vacon Incorporated All Rights Reserved
721 DI1 Configure
722 DI2 Configure
723 DI3 Configure
724 DI4 Configure
725 DI5 Configure
727 MOL Configure
Default: Preset 1
Default: Preset 2
Default: Preset 3
Default: Alt Ramp
Default: Fault Reset
Default: MOL
Range: n/a
Level 2
Parameters
721-725
all configure the function that the digital inputs DI1-5 will perform when active. Parameter
727
,
MOL Configure
726
, MOL Polarity. The options for parameters
721-725
, and for parameter
727
are:
Parameter Value
Description
Preset 1
Preset Speed Input 1 (PS1).
Preset 2
Preset Speed Input 2 (PS2).
Preset 3
Preset Speed Input 3 (PS3).
Coast Stop
Activates a Coast-to-Stop condition.
DC Inject
Begins DC injection braking.
Loc/Rem
Switches from Local to Remote mode.
Alt Ramp
Activates Alternate Ramp.
Fault Reset
Resets a fault.
EMOP+
EMOP increases speed.
EMOP-
EMOP decreases speed.
PID Enable
Enables PI control.
Ref Switch
Switches speed reference signals.
Cur Lim Dis
Disables Current Limit mode.
SL Override
Takes control away from the serial link.
Seq 1
Sequencer input 1.
Seq 2
Sequencer input 2.
Seq 3
Sequencer input 3.
Seq Dwell
Sequencer dwell mode (pause).
Seq Advance
Sequencer advance (skip).
FLY Dis
Disable Catch-on-fly operation.
CurLimIMax
Maximum current limit value is selected when input is active.
MOL
Motor Overload input for external customer connection.
JOG FWD
Sets Jog to forward motion.
JOG REV
Sets Jog to reverse motion.
Not Assigned
Preset 4
Preset Speed Input (PS4).
TOD Ovrride
Indicates the clock function is being manually overridden.
User Flt 1
Trips the drive with User Fault #1.
User Flt 2
Trips the drive with User Fault #1.
Seq 4
Sequencer input 4.
Seq 5
Sequencer input 5.
Seq Trm Run
Sequencer terminal run is active.
AltRamp2
Activates Alternate Ramp 2.
Reset Rem 1
Resets Reminder 1
Reset Rem 2
Resets Reminder 2
Reset Rem 3
Resets Reminder 3
Rem 1 Gate
A digital input has triggered the gate for Reminder #1.
Rem 2 Gate
A digital input has triggered the gate for Reminder #2.
Rem 3 Gate
A digital input has triggered the gate for Reminder #3.
Table 7-2: Description of X5 Parameters