X5 AC Drive User’s Manual
Chapter 7: X5 Parameters
DPD00089A
-
97 -
© 2009 Vacon Incorporated All Rights Reserved
743 Thres 2 Select
Default: 15 (Curr High)
Range: n/a
Level 2
This parameter selects the type of threshold to be used for Threshold 2.
Parameter Value Description
Parameter Value Description
0
Vin 1 High
11
Load In
1
Vin 1 Low
12
Power High
2
Vin 1 In
13
Power Low
3
Vin 2 High
14
Power In
4
Vin 2 Low
15
Curr High
5
Vin 2 In
16
Curr Low
6
Cin High
17
Curr In
7
Cin Low
18
Enc % High
8
Cin In
19
Enc % Low
9
Load High
20
Enc % In
10
Load Low
For detailed information about setting up Threshold parameters, see
744 Thres 2 High
Default: 100.00%
Range: -300.00% to 300.00%
Level 2
This parameter sets the High Thres level for Threshold 2. For detailed information about setting up Threshold
parameters, see
745 Thres 2 Low
Default: 0.00%
Range: -300.00% to 300.00%
Level 2
This parameter sets the Low Thres level for Threshold 2. For detailed information about setting up Threshold
parameters, see
746 Timer 1 Type
Default: 0 (On Delay)
Range: n/a
Level 2
This parameter defines the configuration of Timer #1 that you want the drive to emulate.
Parameter Value Description
0
On Delay
1
Off Delay
2
On/Off Delay
For detailed information about setting up Timer parameters, see
747 Timer 1 Signal
Default: DI-REV
Range: n/a
Level 2
This parameter selects the function that the timer is counting; it includes any function listed in the digital input list.
See Parameter
, Relay 1 Select, on page 93 for the list of options. For detailed information about setting up Timer
parameters, see
748 Timer 1 Time
Default: 1.0 sec
Range: 0.0-320.0 sec
Level 2
This parameter specifies the duration of time in seconds for the timer to count. For detailed information about setting up
Timer parameters, see
.
749 Timer 2 Type
Default: 0
Range: n/a
Level 2
This parameter selects the kind of timer to be used, as shown in the following options:
Parameter Value Description
0
On Delay
1
Off Delay
2
On/Off Delay
For detailed information about setting up Timer parameters, see
Table 7-2: Description of X5 Parameters