X5 AC Drive User’s Manual
Chapter 7: X5 Parameters
DPD00089A
-
84 -
© 2009 Vacon Incorporated All Rights Reserved
417 Accel Time 4
Default: 15.0 s
Range: 0.1 to 3200.0 s
Level 2
302 (Max Frequency)
. This acceleration ramp is selected by parameter
401 (Ramp Select)
or Sequencer Configuration.
Note that extremely short acceleration times may result in nuisance fault trips.
418 Decel Time 4
Default: 15.0 s
Range: 0.1 to 3200.0 s
Level 2
to 0 Hz. This deceleration ramp is selected by parameter
401 (Ramp Select)
or Sequencer Configuration.
Note that extremely short deceleration times may result in nuisance fault trips or may require an external dynamic brake
or regen current limit.
490 Appl Macro
Default: 0 (Factory)
Range: n/a
Macro
This parameter configures what macro will be active in the drive. A macro will change a default or the visibility of a
parameter.
Parameter Value
Description
0
Factory
1
Fan
2
Fan w/ PID
3
Pump
4
Pump w/ PID
5
Vector
491 Seq Appl
Default: 0 (Disabled)
Range: n/a
Macro
This parameter configures whether sequencer parameters are visible, and it also defines the time base of the
sequencer. The time base may change depending on the drive’s timing loops.
Parameter Value
Description
0
Disabled
1
1 sec base
2
.1 sec base
3
.01 sec base
492 SIO Visible
Default: 0 (No)
Range: n/a
Macro
This parameter configures whether SIO parameters are visible.
Options are 0 (No) and 1 (Yes).
The following parameters are made visible if this option is set to
Yes
:
SIO Protocol (900)
Status Word (908)
FBus Write 3 (892)
SIO Baudrate (901)
FBus Read 1 (880)
FBus Write 4 (893)
Comm Drop # (902)
FBus Read 2 (881)
FBus Write 5 (894)
Infrared Baud (916)
FBus Read 3 (882)
SIO Vmet Level (920)
SIO Timer (903)
FBus Read 4 (883)
SIO Imet Level (921)
SIO Cntl Word (904)
FBus Read 5 (884)
Status Word 2 (926)
Ext Ref Freq 1 (905)
FBus Write 1 (890)
Cntl Word 2 (907)
Ext Ref Freq 2 (906)
FBus Write 2 (891)
FBus Port Config (917)
Table 7-2: Description of X5 Parameters