X5 AC Drive User’s Manual
Chapter 7: X5 Parameters
DPD00089A
-
91 -
© 2009 Vacon Incorporated All Rights Reserved
613 Max Regen Ramp
Default: 300%
Range: 100 - 1001%
Level 2
This parameter operates as a percentage of the longest ramp time. This time then defines the amount of time a
deceleration to stop can take without causing a “Regen Timeout” fault. For example, if “Decel Time 1” is 5.0 seconds,
“Decel Time 2” is 10.0 seconds, and “Max Regen Ramp” is 300%, a deceleration to stop that takes more than 30
seconds will cause a “Regen Timeout” fault in the drive.
614 Stability Gain
615 Stability Rate
Default: Model dependent
Range: 0-10
Range: 0-1000
Level 2
Both of these parameters can be used to resolve stability problems if they occur. Use Parameter 615 if the load has
significant inertia with respect to the motor itself.
700 Vmet Config
Default: Freq Out
Range: n/a
Levels 1,2
This parameter configures the analog signal that will be applied to the Vmet output pin.
The following data values may be assigned to this parameter:
Para. Value
Description
Range Limit
Freq Out
Output frequency of the drive
Parameter max freq.
Voltage Out
Voltage being supplied to the motor
Rated motor voltage
Current Out
Current being supplied to the motor
200% of drive rating
Drive Load
Calculated percentage of drive rating
200% of drive rating
Drive Temp
Calculation of total drive temp rating
100% of unit temp rating
Stator Freq
Commanded frequency
100% of input config
Power Out
Calculated power output of drive
250% of drive rating
+/- Load
Percentage torque of drive
-200 to +200% of drive rating
105
)
PID Fback
Allows the analog output to produce
a signal in proportion to the PID
feedback received.
Vin 1
Mirrors the status of the Vin1 input
910
)
0-100%
Cin
Mirrors the status of the Cin input
911
)
0-100%
Vin 2
Mirrors the status of the Vin2 input
912
)
0-100%
SIO Config
Allows the serial port to set the Vmet
analog output through parameter
(SIO Vmet Level)
907 (Control Word 2)
Encoder
Monitors the status of an encoder
connected to the drive through an option
board.
701 Vmet Span
Default: 100%
Range: 0.0%-200.0%
Level 2
This parameter sets the span of the Vmet analog output.
Table 7-2: Description of X5 Parameters
(Page 21 of 40)
Содержание X5
Страница 1: ...X5 AC Drive user s manual ...
Страница 4: ......
Страница 125: ...X5 AC Drive User s Manual Chapter 7 X5 Parameters DPD00089A 123 2009 Vacon Incorporated All Rights Reserved ...
Страница 126: ...X5 AC Drive User s Manual Chapter 7 X5 Parameters DPD00089A 124 2009 Vacon Incorporated All Rights Reserved ...
Страница 138: ......
Страница 140: ......