X5 AC Drive User’s Manual
Chapter 7: X5 Parameters
DPD00089A
-
82 -
© 2009 Vacon Incorporated All Rights Reserved
404 Accel Time 2
Default: 3.0 s
Range: 0.1 to 3200.0 s
Level 2
302 (Max Frequency)
. This acceleration ramp is selected by parameter
401 (Ramp Select)
or Sequencer Configuration.
Note that extremely short acceleration times may result in nuisance fault trips.
405 Decel Time 2
Default: 3.0 s
Range: 0.1 to 3200.0 s
Level 2
to 0 Hz. This deceleration ramp is selected by parameter
401 (Ramp Select)
or Sequencer Configuration.
Note that extremely short deceleration times may result in nuisance fault trips or may require an external dynamic brake
or regen current limit.
406 DC Inject Config
Default: DC at Stop
Range: n/a
Level 2
DC injection braking may be used to stop the motor more quickly than is possible by either a ramp-to-stop or a coast-
to-stop. The X5 drive allows DC braking to be initiated either when a digital input assigned to DC braking becomes true,
when a specified frequency is reached, or when either of these events occurs.
When using a digital input for DC braking, you must use one of the DI parameters to configure the selected digital input
for DC braking. The amount of braking force is set by parameter
408 (DC Inject Level)
407
(DC Inject Time)
.
409 (DC Inj Freq)
. If the frequency at the time of a Stop command is less than that
of
DC Inj Freq
, DC braking begins immediately. The braking continues for the time period specified by parameter
DC
Inj Freq
. Once the time period elapses, the drive may be restarted.
Parameter Value
Description
DC at Stop
DC inject only on Stop
DC at Start
DC inject only on Start
DC at Both
DC inject only on both Start and Stop
DC on Freq
DC inject only on Stop below the set frequency
407 DC Inject Time
Default: 0.2 sec
Range: 0.0 to 5.0 sec
Level 2
If parameter
406
is set to DC at Stop (see page 82), direct current is applied to the motor. This parameter,
DC Inject
Time
, determines how long the direct current will be applied, and how long DC is applied at Start if programmed
accordingly.
This parameter works in tandem with parameter
410 (DC Inject Config)
and the other parameters associated with DC
Inject Config. That is, the time period configured by this parameter,
DC Inject Time
, determines how long DC injection
braking will be active. When DC injection braking is controlled by a digital input, the braking continues for as long as the
digital input is true,
plus
the time set by parameter
407 (DC Inject Time)
. When it is controlled by frequency, however,
it continues for the length of time once the drive reaches the frequency set by parameter
409 (DC Inj Freq)
.
408 DC Inject Level
Default: 50.0%
Range: 0.0% to 100.0%
Level 2
Configures the amount of DC injection that will occur when direct current is injected into the motor windings, which acts
as a braking force. The amount of current is expressed as a percentage of nominal motor current. The braking force
may be applied when starting or stopping. If this parameter is set to 0.0%, the DC injection is disabled.
409 DC Inj Freq
Default: 0 Hz
Range: 0.0 to 20.0 Hz
Level 2
Configures the frequency under which direct current will be applied to the drive when
DC Inject Config
is set to “DC on
Freq.” If this parameter is set to 0.0, the parameter operates in the same way as “DC at Stop.”
Table 7-2: Description of X5 Parameters
(Page 12 of 40)