Safe Torque Off
vacon • 100
Service support: find your nearest Vacon service center at www.vacon.com
9
9.5
Connections
To make the STO function available and ready to be used, both the STO jumpers have to be removed.
They have been located in front of the STO terminal to mechanically prevent the insertion of the STO
inputs. For the correct configuration, see the following table and the Figure 52.
Figure 52. Removing the STO jumpers.
The following examples show the basic principles for wiring the STO inputs and the STO output
feedback. Local standards and regulations should be always followed in the final design.
Signal
Terminal
Technical information
Data
STO1
S1
Insulated digital input 1
(interchangeable polarity)
24V
±20%
10...15 mA
G1
STO 2
S2
Insulated digital input 2
(interchangeable polarity)
24V
±20%
10...15 mA
G2
STO
feedback
F+
Insulated digital output for STO
feedback
(CAUTION! Polarity must be
respected)
24V
±20%
15 mA max.
F-
GND
Table 46. STO connector and data signals.
Make sure that the frequency converter is switched off before cabling.
When the STO function is used, the drive has to be mounted in an enclosure which
fulfils
the requirements for IP54
.
Disconnect both the STO jumpers to allow the cabling of the terminals.
Содержание 20 CP
Страница 1: ...vacon 20 cp ac drives installation Technical and Maintenance manual ...
Страница 2: ......
Страница 6: ...vacon 3 ...
Страница 16: ...1 vacon 13 Safety Figure 6 STO certificate ...
Страница 18: ...1 vacon 15 Safety ...
Страница 24: ...vacon 21 Receipt of delivery 2 ...
Страница 36: ...3 vacon 33 Mounting ...
Страница 48: ...4 vacon 45 Power cabling ...
Страница 64: ...5 vacon 61 Control unit ...
Страница 111: ...Safe Torque Off vacon 108 Service support find your nearest Vacon service center at www vacon com 9 ...