Safety
vacon • 8
Service support: find your nearest Vacon service center at www.vacon.com
1
Figure 2.Protective earthing connections MS2, single-phase version.
The cross-sectional area of every protective earthing conductor which does not form a part of
the supply cable or cable enclosure shall, in any case, be not less than:
•
2.5 mm
2
if mechanical protection is provided or
•
4 mm
2
if mechanical protection is not provided. For cord-connected equipment, provi-
sions shall be made so that the protective earthing conductor in the cord shall, in the
case of failure of the strain-relief mechanism, be the last conductor to be interrupted.
However, always follow the local regulations for the minimum size of the protective earthing
conductor.
NOTE:
Due to the high capacitive currents present in the AC drive, fault current protective
switches may not function properly.