Power cabling
vacon • 36
Service support: find your nearest Vacon service center at www.vacon.com
4
4.1
Circuit breaker
Please disconnect the drive via an external circuit breaker. You have to provide a switching de-
vice between supply and main connection terminals.
When connecting the input terminals to the power supply using a circuit breaker, observe that
this is of
type B or type C
and ensure is has a
capacity of 1.5 to 2 times the inverter’s rated
current
(see Table 30).
NOTE:
circuit breaker is not allowed in installations where C-UL is required. Only fuses are
recommended.
4.2
UL standards on cabling
To meet the UL (Underwriters Laboratories) regulations, use a UL-approved copper cable with
a minimum heat-resistance of 75°C. Use Class 1 wire only.
The units are suitable for use on a circuit capable of delivering no more than 50,000 rms sym-
metrical amperes, 600V AC maximum, when protected by T or J class fuses.
Integral solid state short circuit protection does not provide branch circuit pro-
tection. Branch circuit protection must be provided in accordance with the
National Electrical Code
and any additional local codes.
Содержание 20 CP
Страница 1: ...vacon 20 cp ac drives installation Technical and Maintenance manual ...
Страница 2: ......
Страница 6: ...vacon 3 ...
Страница 16: ...1 vacon 13 Safety Figure 6 STO certificate ...
Страница 18: ...1 vacon 15 Safety ...
Страница 24: ...vacon 21 Receipt of delivery 2 ...
Страница 36: ...3 vacon 33 Mounting ...
Страница 48: ...4 vacon 45 Power cabling ...
Страница 64: ...5 vacon 61 Control unit ...
Страница 111: ...Safe Torque Off vacon 108 Service support find your nearest Vacon service center at www vacon com 9 ...